| Plan Review Notes For Permit 05120172 |
| Permit Number |
05120172 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-05 00:00:00 | ********* UNSAT *********** | | | | | | 1)NOTE: PLEASE SUBMIT THE MANUFCATURES | | | CUT/SPEC SHEETS FOR THE NEW PROPOSED | | | ATS. PLEASE BE SURE A LISITNG FROM A | | | NRTL IS SHOWN. | | | | | | 2)NOTE: PLEASE PROVIDE A MEANS OF | | | SHUTTING OFF THE FUEL SOURCE FOR GEN AT | | | THE GROUND FLR LOCATION OF EXISTING | | | MAINS FOR BLDG. THIS MEANS SHOULD BE | | | READILY ACCESSIBLE FOR SHUTTING DOWN THE | | | FUEL SUPPLY FOR THE GEN, INCLUSIVE OF | | | NAT GAS AND LP. 445.18 | | | | | | 3)NOTE: PLEASE BE SURE TO SPECIFY IF GEN | | | WILL OR WILL NOT BE SEPARATELY DERIVED. | | | 250.30, ETC | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. PLEASE BE SURE TO SEE ANY OTHER | | | POSSIBLE COMMENTS FROM OTHER REVIEWER(S) | | | WHICH MAY AFFECT ELECTRICAL PLANS. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|