Plan Review Notes
Plan Review Notes For Permit 05120172
Permit Number 05120172
Review Stop E
Sequence Number 1
Notes
Date Text
2006-01-05 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SUBMIT THE MANUFCATURES
 CUT/SPEC SHEETS FOR THE NEW PROPOSED
 ATS. PLEASE BE SURE A LISITNG FROM A
 NRTL IS SHOWN.
  
 2)NOTE: PLEASE PROVIDE A MEANS OF
 SHUTTING OFF THE FUEL SOURCE FOR GEN AT
 THE GROUND FLR LOCATION OF EXISTING
 MAINS FOR BLDG. THIS MEANS SHOULD BE
 READILY ACCESSIBLE FOR SHUTTING DOWN THE
 FUEL SUPPLY FOR THE GEN, INCLUSIVE OF
 NAT GAS AND LP. 445.18
  
 3)NOTE: PLEASE BE SURE TO SPECIFY IF GEN
 WILL OR WILL NOT BE SEPARATELY DERIVED.
 250.30, ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE BE SURE TO SEE ANY OTHER
 POSSIBLE COMMENTS FROM OTHER REVIEWER(S)
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]