2006-02-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05120172
 ADD: 2800 N FLAGLER (ROOF)
 CONT: J COMPTON ELEC.
 TEL: (954)219-9011
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
  
 1) PLANS DO NOT INDICATE HOW THE
 GENERATOR WILL RESIST MOMENT OF
 OVERTURNING.106.1.2 ADDITIONAL
 DATA. THE BUILDING OFFICIAL MAY REQUIRE
 DETAILS, COMPUTATIONS, STRESS DIAGRAMS,
 AND OTHER DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
 1604.4 ANALYSIS.
 LOAD EFFECTS ON STRUCTURAL MEMBERS AND
 THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE
 INTO ACCOUNT EQUILIBRIUM, GENERAL
 STABILITY, GEOMETRIC COMPATIBILITY AND
 BOTH SHORT- AND LONG-TERM MATERIAL
 PROPERTIES.
 MEMBERS THAT TEND TO ACCUMULATE RESIDUAL
 DEFORMATIONS UNDER REPEATED SERVICE
 LOADS SHALL HAVE INCLUDED IN THEIR
 ANALYSIS THE ADDED ECCENTRICITIES
 EXPECTED TO OCCUR DURING THEIR SERVICE
 LIFE.
 ANY SYSTEM OR METHOD OF CONSTRUCTION TO
 BE USED SHALL BE BASED ON A RATIONAL
 ANALYSIS IN ACCORDANCE WITH
 WELL-ESTABLISHED PRINCIPLES OF
 MECHANICS. SUCH ANALYSIS SHALL RESULT IN
 A SYSTEM THAT PROVIDES A COMPLETE LOAD
 PATH CAPABLE OF TRANSFERRING LOADS FROM
 THEIR POINT OF ORIGIN TO THE
 LOAD-RESISTING ELEMENTS.
 THE TOTAL LATERAL FORCE SHALL BE
 DISTRIBUTED TO THE VARIOUS VERTICAL
 ELEMENTS OF THE LATERAL-FORCE-RESISTING
 SYSTEM IN PROPORTION TO THEIR RIGIDITIES
 CONSIDERING THE RIGIDITY OF THE
 HORIZONTAL BRACING SYSTEM OR DIAPHRAGM.
 RIGID ELEMENTS THAT ARE ASSUMED NOT TO
 BE A PART OF THE LATERAL-FORCE-RESISTING
 SYSTEM SHALL BE PERMITTED TO BE
 INCORPORATED INTO BUILDINGS PROVIDED
 THAT THEIR EFFECT ON THE ACTION OF THE
 SYSTEM IS CONSIDERED AND PROVIDED FOR IN
 DESIGN. PROVISIONS SHALL BE MADE FOR THE
 INCREASED FORCES INDUCED ON RESISTING
 ELEMENTS OF THE STRUCTURAL SYSTEM
 RESULTING FROM TORSION DUE TO
 ECCENTRICITY BETWEEN THE CENTER OF
 APPLICATION OF THE LATERAL FORCES AND
 THE CENTER OF RIGIDITY OF THE
 LATERAL-FORCE-RESISTING SYSTEM.
 EVERY STRUCTURE SHALL BE DESIGNED TO
 RESIST THE OVERTURNING EFFECTS CAUSED BY
 THE LATERAL FORCES SPECIFIED IN THIS
 CHAPTER. SEE SECTION 1609 FOR WIND AND
 SECTION 1610 FOR LATERAL SOIL LOADS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  