| Date |
Text |
| 2006-07-05 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1) PROVIDE 2 COMPLETE SETS OF DRAWINGS |
| | WITH PERMIT APPLICATION PER 106.1 FBC |
| | NOTE INSERT "AS BUILTS" OF EXISTING |
| | BLDG,ELEC, PLUMB & MECH INTO |
| | CONSTRUCTION PLAN SETS. BE SURE THAT |
| | THEY ARE SIGNED BY THE RESPONSIBLE PARTY |
| | |
| | 2) SUBMIT ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND |
| | DATED BY PREPARER AND OWNER/AGENT PRIOR |
| | TO SUBMITTAL. NOTE CALC'S NOT SIGNED BY |
| | OWNER/AGENT |
| | |
| | 3) GENERAL CONTRACTOR CANNOT INSTALL |
| | FLAT ROOFING PRODUCT AS IT IS OUTSIDE |
| | SCOPE OF LICENCE PER 489.113(3B,G)F.S. |
| | |
| | 4) THE PERMIT APPLICATION SHALL INCLUDE |
| | TWO COPIES OF EACH PRODUCT APPROVAL THAT |
| | |
| | IS RELEVANT PER 9B-72. THESE SHOULD |
| | INCLUDE THE FLORIDA STATE APPROVAL COVER |
| | PAGES, AND THE PRODUCT NOA THAT LISTS |
| | THE SYSTEM COMPONENTS/ FASTENER LIST |
| | PAGES, THE PAGES WITH THE CHOSEN |
| | ASSEMBLY/ SYSTEM TO BE USED AND THE |
| | GENERAL LIMITATIONS PAGE. ALL CAN BE |
| | FOUND ON WWW.FLORIDABUILDING.ORG |
| | NOTE 2 COPIES OF THE FLORIDA COVERS ARE |
| | REQUIRED ALONG WITH 2 COPIES OF THE NOA |
| | THAT THE FLORIDA STATE APPROVAL WAS |
| | BASED ON |
| | |
| | A) STORM PANELS REQUIRE 2 COPIES OF |
| | COVER AND 2 COPIES OF DRAWING # 05-422 |
| | (SEE PDF FILE UNDER EVALUATION REPORTS) |
| | PLEASE MARK THE DRAWINGS WITH THE |
| | METHOD, ANCHOR TYPE, ETC THAT WILL BE |
| | USED FOR INSTALLATION |
| | |
| | B) SINGLE HUNG WINDOWS REQUIRE 2 COPIES |
| | OF STATE COVER AND 2 COPIES OF NOA |
| | (SEE PDF FILE NOA# 05-0279.03) |
| | |
| | C) WHERE WINDOWS ARE PAIRED TOGETHER |
| | MULLIONS ARE REQUIRED SUBMIT 2 COPIES OF |
| | STATE COVERS AND THE EVAL/NOA'S FOR THE |
| | MULLIONS |
| | |
| | D) DOOR REQUIRES 2 COPIES OF STATE COVER |
| | FL# 539-R1 |
| | |
| | E) BUILT UP ROOFING REQUIRES 2 COPIES OF |
| | STATE COVER SHEETS |
| | |
| | F) PROVIDE WOOD CONNECTOR INDEX WITH |
| | CONNECTORS THAT WILL BE USED AND THEIR |
| | FL# MARKED (SEE ATTACHED SHEET) |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |