2005-12-28 00:00:00********** UNSAT *************
  
  
 1)NOTE: PLEASE SUBMIT COMPLETE PLANS FOR
 REVIEW MEETING MIN 2002 NEC CODE
 COMPLIANCE.
 PLEASE SEE RISER SUBMITTED DOES NOT
 INLCUDE, CONDUCTORS, CONDUIT SIZES,
 GROUNDING, LOAD CALCULATIONS ETC ETC.
 215.5,225.31-225.39, 230.72, 250.50,
 250.30, 702.5 ,,,,,
  
 2)NOTE: PLEASE SEE PLANS SHALL BE OF
 DRAFTSMAN QUALITY PER FBC ADMINISTRATIVE
 SECTION 106.1.3
  
 3)NOTE: PLEASE SEE VALUATION IS BASED ON
 ALL LABOR AND MATERIALS, EVEN IF ANY
 EQUIPMENT IS OWNER SUPPLIED.
 108.3
  
 4)NOTE: PLEASE SUBMIT A LAYOUT OF HOUSE
 FOR LOCATION OF GEN, MAINS(S), GEN,
 PANELS ETC.
 SEE OTHER REVIEWER(S) COMMENTS WITH
 RESPECT TO MIN DISTANCE TO BE SHOWN FROM
 VENTED OPENINGS, WINDOWS ETC IN
 DWELLING.
  
 PLEASE KNOW, A COMPLETE REVIEW FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  