| Notes |
| Date |
Text |
| 2005-12-28 00:00:00 | ********** UNSAT ************* | | | | | | | | | 1)NOTE: PLEASE SUBMIT COMPLETE PLANS FOR | | | REVIEW MEETING MIN 2002 NEC CODE | | | COMPLIANCE. | | | PLEASE SEE RISER SUBMITTED DOES NOT | | | INLCUDE, CONDUCTORS, CONDUIT SIZES, | | | GROUNDING, LOAD CALCULATIONS ETC ETC. | | | 215.5,225.31-225.39, 230.72, 250.50, | | | 250.30, 702.5 ,,,,, | | | | | | 2)NOTE: PLEASE SEE PLANS SHALL BE OF | | | DRAFTSMAN QUALITY PER FBC ADMINISTRATIVE | | | SECTION 106.1.3 | | | | | | 3)NOTE: PLEASE SEE VALUATION IS BASED ON | | | ALL LABOR AND MATERIALS, EVEN IF ANY | | | EQUIPMENT IS OWNER SUPPLIED. | | | 108.3 | | | | | | 4)NOTE: PLEASE SUBMIT A LAYOUT OF HOUSE | | | FOR LOCATION OF GEN, MAINS(S), GEN, | | | PANELS ETC. | | | SEE OTHER REVIEWER(S) COMMENTS WITH | | | RESPECT TO MIN DISTANCE TO BE SHOWN FROM | | | VENTED OPENINGS, WINDOWS ETC IN | | | DWELLING. | | | | | | PLEASE KNOW, A COMPLETE REVIEW FOR CODE | | | COMPLIANCE CAN NOT BE DONE AT THIS TIME. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|