| Plan Review Notes For Permit 05120123 |
| Permit Number |
05120123 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-12 00:00:00 | *** DENIED *** | | | 1) NEED TO SUBMIT MANUAL J CALCULATIONS. | | | 2) SHOW SENSIBLE BTU'S ON PLANS ALSO. | | | 3) SHOW AHU'S TOTAL CFM'S ON PLANS. | | | 4) EXPLAIN WHERE CONDENSATE DRAIN IS | | | DISCHARGING TO. | | | 5) SHOW WHERE SECONDARY DRAIN LINE GOES | | | TO, OR IF A FLOAT SWITCH IS BEING USED. | | | 6) RETURN AIR GRILLS AND SUPPLY AIR | | | GRILLS NEED TO BE SIZED. | | | 7) RETURN AIR DUCTS IN OFFICE 6,7,AND 8 | | | ARE NOT SIZED. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|