| Plan Review Notes For Permit 05120096 |
| Permit Number |
05120096 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-01-06 00:00:00 | DENIED | | | | | | 1) THE NOA THAT IS PART OF THE STATE | | | PRODUCT APPROVAL FOR THE POLYGLASS | | | MODIFIED ROOF SYSTEM LISTS A MAXIMUM | | | DESIGN PRESSURE OF -45 PSF FOR THE | | | APPROVED ASSEMBLY THAT WAS SUBMITTED. | | | THE NOA FOR THIS SYSTEM SPECIFIES | | | GENERAL LIMITATION #9, WHICH DOES NOT | | | ALLOW THE PRESSURE TO BE INCREASED BY | | | ENHANCED FASTENING. THEREFORE, THE | | | ENGINEERING DOES NOT WORK FOR THIS | | | PRODUCT. PLEASE SEE NOA THAT WAS | | | SUBMITTED. | | | | | | 2) THE ENGINEERING IS MIXING CRITERIA | | | FROM TWO NOAS AND DIFFERENT ASSEMBLIES. | | | | | | 3)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|