| Plan Review Notes For Permit 05120096 |
| Permit Number |
05120096 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-30 00:00:00 | DENIED | | | | | | 1) THE NOA THAT WAS SUBMITTED FOR THE | | | POLYGLASS MODIFIED SYSTEM HAS BEEN | | | REVISED BY NOA 03-0130.08. SEE UPDATED | | | INFORMATION ON STATE PRODUCT APPROVAL | | | WEBSITE AT WWW.FLORIDABUILDING.ORG. | | | | | | 2) ENGINEERING IS BASED ON THE OLD NOA. | | | | | | 3) THE ENGINEERING SUBMITTED DOES NOT | | | CORRESPOND WITH THE ASSEMBLY INDICATED | | | IN THE NOA THAT WAS SUBMITTED. THE NOA | | | IS FOR A NON-INSULATED WOOD DECK WITH | | | -45 PSF DESIGN PRESSURE AND DOES NOT | | | ALLOW ENHANCED FASTENING. ENGINEERING IS | | | FOR INSULATED DECK WITH -60 PSF AND | | | ALLOWS ENHANCED FASTENING. | | | | | | 4) THE MAX PRESSURE IN THE APPLICATION | | | FORM FOR THE METAL ROOF IS FOR STEEL | | | DECKS. SEE NOA. | | | | | | 5) PROVIDE TWO COPIES OF THE FL PRODUCT | | | APPROVAL COVER SHEETS. | | | | | | 6)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|