Plan Review Notes
Plan Review Notes For Permit 05120096
Permit Number 05120096
Review Stop B
Sequence Number 1
Notes
Date Text
2005-12-30 00:00:00DENIED
  
 1) THE NOA THAT WAS SUBMITTED FOR THE
 POLYGLASS MODIFIED SYSTEM HAS BEEN
 REVISED BY NOA 03-0130.08. SEE UPDATED
 INFORMATION ON STATE PRODUCT APPROVAL
 WEBSITE AT WWW.FLORIDABUILDING.ORG.
  
 2) ENGINEERING IS BASED ON THE OLD NOA.
  
 3) THE ENGINEERING SUBMITTED DOES NOT
 CORRESPOND WITH THE ASSEMBLY INDICATED
 IN THE NOA THAT WAS SUBMITTED. THE NOA
 IS FOR A NON-INSULATED WOOD DECK WITH
 -45 PSF DESIGN PRESSURE AND DOES NOT
 ALLOW ENHANCED FASTENING. ENGINEERING IS
 FOR INSULATED DECK WITH -60 PSF AND
 ALLOWS ENHANCED FASTENING.
  
 4) THE MAX PRESSURE IN THE APPLICATION
 FORM FOR THE METAL ROOF IS FOR STEEL
 DECKS. SEE NOA.
  
 5) PROVIDE TWO COPIES OF THE FL PRODUCT
 APPROVAL COVER SHEETS.
  
 6)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714