| Date |
Text |
| 2007-04-16 16:33:22 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE THERE IS NOW A PANEL BEING ADDED | | | FOR POOL EQUIPMENT; HOWEVER THE PANEL IS NOT ON RISER | | | AND NOT SHOWN PLANS FOR LOCATION. | | | PLEASE ALSO SEE THAT THE PANEL SCHEDULE SEEMS TO ONLY | | | SHOW ON SIDE OF THE PANEL. PLEASE LABEL CIRCUITS AS | | | DONE ON PANELS A1 AND B. | | | 215.5, 408.4 ETC | | | FBC106.3.5.4 | | | | | | 2) NOTE: PLEASE SEE NEW PANEL SCHEDULE FOR METER/MAIN | | | WHICH INDICATES 2/0'S FOR THE SUB PANELS A1 AND B, YET | | | THE RISER SHOWS #1'S. IF THE CONDUCTORS ARE INDEED | | | 2/0'S THEN THE CONDUIT SIZE AS SHOWN IS NOT LARGE | | | ENOUGH. | | | PLEASE ADJUST AND CORRELATE PLANS. | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|