Plan Review Notes
Plan Review Notes For Permit 05120081
Permit Number 05120081
Review Stop P
Sequence Number 3
Notes
Date Text
2006-06-26 00:00:00******REVISION DENIED******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR THE PLUMBING
 REVISION:
  
 1.PER FBC-2004, CHAPTER 1,SECTION
 106.3.5.4 RESIDENTIAL (ONE AND TWO
 FAMILY) SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM CLEARLY
 INDICATING ALL FIXTURES, WASTE, VENTS,
 TRAPS WITH SIZES, AND CLEANOUT
 LOCATIONS. PLEASE SEE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
 2.PLEASE SEE THE CORRECTED DRAWING IN
 RED INK INDICATING ALL CLEANOUTS ON THE
 SANITARY ISOMETRIC RISER DIAGRAM PER THE
 FOLLOWING.
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
 (B) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM) PLEASE
 NOTE THE WASHING MACHINE CLEANOUT SIZE
 AS 3".
 (C) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS. PLEASE NOTE
 THE WASHING MACHINE CLEANOUT LOCATION AS
 48" ABOVE FINNISH FLOOR.
 3. PLEASE INDICATE ON THE SANITARY RISER
 DIAGRAM THE AUTOMATIC AIR VENTS (SV) AND
 THE SIZE AND "VENT THROUGH ROOF" (VTR)
 LOCATIONS PER THE CORRECTED DRAWING IN
 RED INK.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  