| 2006-06-26 00:00:00 | ******REVISION DENIED****** |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR PLAN REVIEW FOR THE PLUMBING |
| | REVISION: |
| | |
| | 1.PER FBC-2004, CHAPTER 1,SECTION |
| | 106.3.5.4 RESIDENTIAL (ONE AND TWO |
| | FAMILY) SUBMIT A PLUMBING SANITARY |
| | ISOMETRIC RISER DIAGRAM CLEARLY |
| | INDICATING ALL FIXTURES, WASTE, VENTS, |
| | TRAPS WITH SIZES, AND CLEANOUT |
| | LOCATIONS. PLEASE SEE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | 2.PLEASE SEE THE CORRECTED DRAWING IN |
| | RED INK INDICATING ALL CLEANOUTS ON THE |
| | SANITARY ISOMETRIC RISER DIAGRAM PER THE |
| | FOLLOWING. |
| | (A) 708.3.4 BASE OF STACK. A CLEANOUT |
| | SHALL BE PROVIDED AT THE BASE OF EACH |
| | WASTE OR SOIL STACK |
| | (B) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM) PLEASE |
| | NOTE THE WASHING MACHINE CLEANOUT SIZE |
| | AS 3". |
| | (C) 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. PLEASE NOTE |
| | THE WASHING MACHINE CLEANOUT LOCATION AS |
| | 48" ABOVE FINNISH FLOOR. |
| | 3. PLEASE INDICATE ON THE SANITARY RISER |
| | DIAGRAM THE AUTOMATIC AIR VENTS (SV) AND |
| | THE SIZE AND "VENT THROUGH ROOF" (VTR) |
| | LOCATIONS PER THE CORRECTED DRAWING IN |
| | RED INK. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | |
| | END OF COMMENTS: |
| | |