Plan Review Notes
Plan Review Notes For Permit 05120081
Permit Number 05120081
Review Stop E
Sequence Number 3
Notes
Date Text
2006-09-17 00:00:00** UNSAT **
  
 ** PLEASE SEE NOTES BELOW WERE GIVEN ON
 4/3/06 WHICH STILL ARE NEED OF
 ADDRESSING.
  
 ** NEW NOTES
  
 1) NOTE: PLEASE CLARIFY IF THE DINING RM
 IS ON ONE OR "MORE" OF THE SMALL
 APPLIANCE CIRCUITS. PLEASE SEE IF THE
 DINING ROOM IS ON ITS OWN SMALL APPL
 DINING CIRCUIT, PLEASE REVISE PANEL
 SCHEDULE AND LOAD CALCULATIONS PER
 210.52B1,210.11C1,220.16
  
 2) NOTE: PLEASE SEE PLANS SHOW A
 GENERATOR WHICH IS NOT ON RISER AND
 THERE IS CURRENTLY NO RECORD OF A PERMIT
 BEING PULLED TO INSTALL A GENERATOR.
 PLEASE REMOVE. OR NOTE "FUTURE". PLEASE
 KNOW, THE LOCATION OF THE GEN IS
 REQUIRED TO BE 5' FROM BUILDING AND ANY
 SURROUNDIGN STRUCTURES/WALLS/FENCES OR
 PER MANUFACTURES SPEC MIN.
  
 3) NOTE: PLEASE SEE LIVING ROM/ BEDRM #3
 FOR WALL SPACES RECEPT SPACING PER
 210.52.
 6' OF DOOR AND MORE THAN 2' OF WALL
 SPACE.
  
  
 ** PREVIOUS REVIEW NOTES WHICH WERE
 GIVEN AS A "PROVISO".
 PLEASE SEE ALL THE CIRCUITS BEING SHOWN
 AS #12 WITH 15A BREAKERS?
  
  
  
 *** PREVIOUS REVIEW REDLINED NOTES.
  
 *** NOTES REDLINED **
  
 PLEASE SEE MANY 15A CIRCUITS SHOWN WITH
 #12 AWG, THIS IS OK, HOWEVER IF SHOWN
 THIS IS WHAT WILL BE REQUIRED TO BE
 INSTALLED.
  
 PLEASE SEE POOL LTS SHOWN ON 20A CIRCUIT
 W/ #14 AWG. PLEASE SEE 240.4,310.16, MAY
 ONLY BE 15A OCP OR ADJUST AWG TO #12.
  
 PLEASE SEE ALL DISCONNECT'S SHOWN ON
 RISER DIAGRAM WHICH DO NOT INDICATE WHAT
 THEY ARE FEEDING. THESE ARE TO BE
 IDENTIFIED.
  
 PLEASE SUBMIT THE ABOVE CORRECTIONS,
 ALONG WITH ANY OTHER REVISIONS "BEFORE
 ROUGH ELECTRICAL INSPECTION".
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTRACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]