| Plan Review Notes For Permit 05120081 |
| Permit Number |
05120081 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-04-03 00:00:00 | *** NOTES REDLINED ** | | | | | | PLEASE SEE MANY 15A CIRCUITS SHOWN WITH | | | #12 AWG, THIS IS OK, HOWEVER IF SHOWN | | | THIS IS WHAT WILL BE REQUIRED TO BE | | | INSTALLED. | | | | | | PLEASE SEE POOL LTS SHOWN ON 20A CIRCUIT | | | W/ #14 AWG. PLEASE SEE 240.4,310.16, MAY | | | ONLY BE 15A OCP OR ADJUST AWG TO #12. | | | | | | PLEASE SEE ALL DISCONNECT'S SHOWN ON | | | RISER DIAGRAM WHICH DO NOT INDICATE WHAT | | | THEY ARE FEEDING. THESE ARE TO BE | | | IDENTIFIED. | | | | | | PLEASE SUBMIT THE ABOVE CORRECTIONS, | | | ALONG WITH ANY OTHER REVISIONS "BEFORE | | | ROUGH ELECTRICAL INSPECTION". | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTRACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|