Plan Review Notes
Plan Review Notes For Permit 05120081
Permit Number 05120081
Review Stop E
Sequence Number 2
Notes
Date Text
2006-04-03 00:00:00*** NOTES REDLINED **
  
 PLEASE SEE MANY 15A CIRCUITS SHOWN WITH
 #12 AWG, THIS IS OK, HOWEVER IF SHOWN
 THIS IS WHAT WILL BE REQUIRED TO BE
 INSTALLED.
  
 PLEASE SEE POOL LTS SHOWN ON 20A CIRCUIT
 W/ #14 AWG. PLEASE SEE 240.4,310.16, MAY
 ONLY BE 15A OCP OR ADJUST AWG TO #12.
  
 PLEASE SEE ALL DISCONNECT'S SHOWN ON
 RISER DIAGRAM WHICH DO NOT INDICATE WHAT
 THEY ARE FEEDING. THESE ARE TO BE
 IDENTIFIED.
  
 PLEASE SUBMIT THE ABOVE CORRECTIONS,
 ALONG WITH ANY OTHER REVISIONS "BEFORE
 ROUGH ELECTRICAL INSPECTION".
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTRACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]