| 2005-12-27 00:00:00 | *** DENIED *** |
| | 1) ENERGY CALCULATIONS NEED TO BE ON |
| | FORM 600A-04 (2004) PER FBC 13-600.3.A . |
| | |
| | 2) ENERGY CALCULATIONS NEED TO BE SIGNED |
| | BY OWNER/AGENT. |
| | |
| | 3) MECHANICAL PLANS MUST BEAR THE NAME |
| | AND SIGNATURE OF THE PERSON RESPONSIBLE |
| | FOR THE DESIGN, PER FBC 104.2.1 . |
| | |
| | 4) NEED TO SUPPLY COMBUSTION AIR FOR GAS |
| | WATER HEATER IN GARAGE, PER 2004 FBC/R |
| | M1701.1, (DID NOT FIND ON ARCHITECTS |
| | PLANS). |
| | |
| | 5) NEED DETAILED MANUFACTURE'S |
| | SPECIFICATION'S AND INSTALLATION |
| | INSTRUCTIONS FOR FIRE PLACE. |
| | |
| | 6) NEED COMBUSTION AIR CAL,S. FOR FIRE |
| | PLACE. |
| | |
| | 7) GRILL IN COVERED PORCH REQUIRES AN |
| | APPROVED EXHAUST HOOD, PER FBC/R M1504.1 |
| | |
| | 8) T-STAT #1 NOT SHOWING ON PLANS. |
| | |
| | 9) RETURN AIR DUCT AND GRILL TO LIBRARY |
| | NOT SIZED. |
| | |
| | 10) RETURN AIR GRILL FOR AHU #2 APPEARS |
| | TO BE TO SMALL FOR A FIVE TON UNIT. |
| | |
| | 11) THE GENERATOR WILL REQUIRE A SEPARET |
| | PERMIT. |
| | |
| | 12) NEED TO FILE A NOTICE OF |
| | COMMENCEMENT, PER F.S. 713.13 . |
| | |
| | 13) NEED TO UP DATE WORKERS COMP. INSUR. |
| | INFO. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |
| | |
| | |
| | |
| | . |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |