| 2005-12-23 00:00:00 | **** UNSAT **** |
| | |
| | 1)NOTE: PLEASE SEE FS 481.221 WHICH |
| | REQUIRES THE PLANS TO BE SIGNED,DATED |
| | AND SAEALED BY SAID ARCHITECT, |
| | (E-SHEETS NOT DONE) |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | PLEASE SEE IT IS NOTED THAT THE AIC |
| | RATING IS ALREADY SHOWN FOR THE SUB |
| | PANELS, JUST NEEDST O BE SHOWN FOR MAIN. |
| | |
| | 3)NOTE: PLEASE SHOW METER MAIN COMBO ON |
| | PLANS ALSO, AS PLANS SHOWS A METER AND A |
| | SEPARATE MAIN DISC. |
| | |
| | 4)NOTE: PLEASE SEE LOCATIONS ON PLANS |
| | FOR MANY MISSING RECEPTS REQUIRED PER |
| | 210.52 |
| | 6' OF DOORS, ETC |
| | PLEASE ALSO SEE WAHT APPEAR TO BE A |
| | "SHIFT" ON THE PLANS FOR ONE OF THE |
| | BEDRMS. |
| | |
| | 5)NOTE: PLEASE INCLUDE ALL ROOM/AREA |
| | DESIGNATIONS ON PLANS. |
| | |
| | 6)NOTE: PLEASE BE SURE TO MOVE ALL SD'S |
| | INTO BEDROOM AREAS,AS SD'S ARE REQUIRED |
| | TO BE WITHIN 12" OF THE HIGHEST POINT OF |
| | A FLAT CEILING. |
| | NFPA-72 11.8.3.5 |
| | |
| | 7)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | PLEASE BE SURE TO CORRELATE THE 60+ |
| | FIXTURES ON PLANS WITH THE LOAD AND |
| | SCHEDULE. |
| | |
| | 8)NOTE: PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE, AS ONLY AFCI PROTECTION IS |
| | SHOWN FOR RECEPTS. |
| | 2002 NEC 210.12, REQUIRES ALL ELECTRICAL |
| | OUTLETS IN BEDRMS TO HAVE ARC FAULT |
| | PROTECTION. SD'S, LTS, FANS, RECEPTS |
| | ETC. |
| | |
| | 9)NOTE: PLEASE SEE 250.66 FOR MIN SIZING |
| | FOR GEC. PLEASE SEE A #2 IS SHOWN TO |
| | CWP, HOWEVER A #4 IS ALSO SHOWN. PLEASE |
| | SEE THE REQUIRED CONTINUOUS GEC SHALL BE |
| | #2 MIN. |
| | |
| | 10)NOTE: PLEASE SEE LAUNDRY RM? , PLEASE |
| | SEE WHAT APPEARS TO BE ONLY A RECEPT FOR |
| | THE WASHER OR DRYER, AS BOTH ARE NOT |
| | SHOWN. |
| | 215.5 |
| | |
| | 11)NOTE: PLEASE SEE MIN CLEARENCE |
| | REQUIRED PER 110.26 FOR CU DISCONNECTS. |
| | |
| | ** PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLU INERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | PLEASE ONLY SUBMIT ONE COPY OF ANY |
| | OLD/VOIDED SHEETS FOR REFERENCE. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |