Plan Review Notes
Plan Review Notes For Permit 05120081
Permit Number 05120081
Review Stop E
Sequence Number 1
Notes
Date Text
2005-12-23 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASE SEE FS 481.221 WHICH
 REQUIRES THE PLANS TO BE SIGNED,DATED
 AND SAEALED BY SAID ARCHITECT,
 (E-SHEETS NOT DONE)
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE SEE IT IS NOTED THAT THE AIC
 RATING IS ALREADY SHOWN FOR THE SUB
 PANELS, JUST NEEDST O BE SHOWN FOR MAIN.
  
 3)NOTE: PLEASE SHOW METER MAIN COMBO ON
 PLANS ALSO, AS PLANS SHOWS A METER AND A
 SEPARATE MAIN DISC.
  
 4)NOTE: PLEASE SEE LOCATIONS ON PLANS
 FOR MANY MISSING RECEPTS REQUIRED PER
 210.52
 6' OF DOORS, ETC
 PLEASE ALSO SEE WAHT APPEAR TO BE A
 "SHIFT" ON THE PLANS FOR ONE OF THE
 BEDRMS.
  
 5)NOTE: PLEASE INCLUDE ALL ROOM/AREA
 DESIGNATIONS ON PLANS.
  
 6)NOTE: PLEASE BE SURE TO MOVE ALL SD'S
 INTO BEDROOM AREAS,AS SD'S ARE REQUIRED
 TO BE WITHIN 12" OF THE HIGHEST POINT OF
 A FLAT CEILING.
 NFPA-72 11.8.3.5
  
 7)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 PLEASE BE SURE TO CORRELATE THE 60+
 FIXTURES ON PLANS WITH THE LOAD AND
 SCHEDULE.
  
 8)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE, AS ONLY AFCI PROTECTION IS
 SHOWN FOR RECEPTS.
 2002 NEC 210.12, REQUIRES ALL ELECTRICAL
 OUTLETS IN BEDRMS TO HAVE ARC FAULT
 PROTECTION. SD'S, LTS, FANS, RECEPTS
 ETC.
  
 9)NOTE: PLEASE SEE 250.66 FOR MIN SIZING
 FOR GEC. PLEASE SEE A #2 IS SHOWN TO
 CWP, HOWEVER A #4 IS ALSO SHOWN. PLEASE
 SEE THE REQUIRED CONTINUOUS GEC SHALL BE
 #2 MIN.
  
 10)NOTE: PLEASE SEE LAUNDRY RM? , PLEASE
 SEE WHAT APPEARS TO BE ONLY A RECEPT FOR
 THE WASHER OR DRYER, AS BOTH ARE NOT
 SHOWN.
 215.5
  
 11)NOTE: PLEASE SEE MIN CLEARENCE
 REQUIRED PER 110.26 FOR CU DISCONNECTS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLU INERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE ONLY SUBMIT ONE COPY OF ANY
 OLD/VOIDED SHEETS FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  