| 2006-01-23 00:00:00 | *********** UNSAT 2ND REVIEW ******* |
| | |
| | |
| | PLEASE SEE COMMENTS FROM PREVIOUS REVIEW |
| | WHICH STILL NEED TO BE ADDRESSED. |
| | |
| | |
| | 1)NOTE: PLEASE SUBMIT PLANS WITH |
| | DRAFTMANS QUALITY. |
| | FBCADMINISTRATIVE CODE 106 |
| | |
| | 2)NOTE: PLEASE SEE VALUATION HAS NOT |
| | BEEN INCREASED AND VALUE SHALL BE |
| | ACCESSED BY THIS OFFICE IF AN |
| | APPROPRIATE VALUE IS ADJUSTED. |
| | PLEASE SEE THE ELECTRICAL WORK ALONE IS |
| | SUBSTANIAL. |
| | FBC 108.3 |
| | |
| | 3)NOTE: PLEASE SEE ALL PLANS SHALL |
| | CONTAIN THE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR SAID |
| | PLANS/DESIGN. |
| | |
| | 4)NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUITING OF EXT AND EM LTS AS ON |
| | PREVIOUS REVIEW. THESE SHALL BE |
| | CIRCUITED TO THE LOCAL LIGHTING BRANCH |
| | CIRCUIT. |
| | PLEASE SEE EM LTS ON WITH RECEPTS. |
| | |
| | 5)NOTE: PLANS SHALL DESIGNATE OCCUPANCY |
| | FOR USE. |
| | |
| | 6)NOTE: PLEASE SEE NOTE #6 FROM PREVIOUS |
| | REVIEW ALSO. |
| | |
| | PLEASE SEE OTHER REVIEWERS COMMENTS. |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | NOTES FOR FIRST REVIEW. |
| | |
| | PLEASE SEE VALUATION FOR SCOPE OF WORK |
| | IS LOW AND MSUT BE INCREASED TO AN |
| | APPROPRIATE VALUE OR ONE SHALL BE |
| | ASSESSED PER MARSHALL'S/ SWIFT GUIDE. |
| | PLEASE KNOW, THE 4X FEE SHALL BE |
| | ADJUSTED UPON VALUE INCREASE AND FEES |
| | WILL BE DUE. |
| | FBC ADMINISTRATIVE SECTION. 108.3 |
| | |
| | 2)NOTE: PLEASE SUBMIT PLANS WITH |
| | DRAFTMANS QUALITY FOR ALL DETAILS AND |
| | SCOPE OF WORK TO BE PERFORMED. |
| | FBC 106 |
| | |
| | 3)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH A PANEL |
| | SCHEDULE TO BE SUBMITTED. |
| | PLEASE SHOW SIZE OF PANEL AND NEW AND |
| | EXISTING LOADS. |
| | 215.5 |
| | PLEASE ALSO SEE 700.12E FOR CIRCUITING |
| | OF EM/EXT LTS. (LOCAL LIGHTING BRNACH |
| | CIRCUIT) |
| | |
| | 4)NOTE: OK. |
| | |
| | 5)NOTE: OK, SEE NEW NOTES |
| | |
| | 6)NOTE: PLEASE SEE PLANS SUBMITTED |
| | MENTIONS: " ALL IMPROVEMENTS ARE |
| | EXISTING. ADDITIONAL DRAWINGS WILL BE |
| | SUBMITTED FOR THE REMAINDER OF PROPOSED |
| | CONSTRUCTION"?? |
| | PLEASE CLARIFY THIS. |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |