| 2005-12-12 00:00:00 | DENIED; | | | 1.HANDICAP TOILETTO BE 1' 6" OFF WALL. | | | FBC-2004 CHAPTER 11 FIG. 30A. | | | 2.TOILET ROOM DOORS SHALL BE LOCATED IN | | | THE CORNER DIAGONAL TO THE DOOR. SEE | | | NOTES BELOW FIG. 30E. | | | 3.WOMANS ROOM LAVITORY TO COMPLY WITH | | | SEC. 11-4.19.3. CLEAR FLOOR SPACE. | | | MIRROR TO COMPLY WITH SEC.11-4.19.6 | | | PLEASE SHOWHIGHT OFF FLOOR. | | | 4.PAGE P-1 PLUMBING NOTE # 26. | | | MECHANICAL VENTS CAN BE USED ONLY ON THE | | | TOP 4 FLOORS PER MANUFACTURE SPECS. | | | PLEASE DELETE NOTE 26. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|