| Plan Review Notes For Permit 05120057 |
| Permit Number |
05120057 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-30 00:00:00 | ******DENIED****** | | | | | | 1) SHT E101 ILLUSTRATES A SINGLE MARKED | | | EXIT. THE CRITERIA IN ACCORDANCE WITH | | | NFPA 101, 2003 EDITION SEC. 38.2.4.3 (1) | | | HAS NOT BEEN MET, RENDERING THIS | | | ARRANGEMENT UNACCEPTABLE. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS | | | REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL. | | | | | | 3) PLEASE INDICATE THE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILING IN | | | TERMS OF CLASS A,B, OR C. | | | | | | 4) 2A-10B,C RATED FIRE EXTINGUISHERS | | | SHALL BE MOUNTED AT DISTANCE TO SATISFY | | | 75' TRAVEL DISTANCE REQUIREMENT. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|