Plan Review Notes
Plan Review Notes For Permit 05120057
Permit Number 05120057
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-12-30 00:00:00******DENIED******
  
 1) SHT E101 ILLUSTRATES A SINGLE MARKED
 EXIT. THE CRITERIA IN ACCORDANCE WITH
 NFPA 101, 2003 EDITION SEC. 38.2.4.3 (1)
 HAS NOT BEEN MET, RENDERING THIS
 ARRANGEMENT UNACCEPTABLE.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 3) PLEASE INDICATE THE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING IN
 TERMS OF CLASS A,B, OR C.
  
 4) 2A-10B,C RATED FIRE EXTINGUISHERS
 SHALL BE MOUNTED AT DISTANCE TO SATISFY
 75' TRAVEL DISTANCE REQUIREMENT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722