Plan Review Notes
Plan Review Notes For Permit 05120057
Permit Number 05120057
Review Stop B
Sequence Number 1
Notes
Date Text
2006-02-07 00:00:001)SHEET A-1 INDICATES FLOOR PLAN FOR
 BARNIES:SHOULD REFLECT SALES OFFICES.
  
 2)CONSTRUCTION SHALL COMPLY WITH THE
 2004 FLORIDA BUILDING CODE/EXISTING
 BUILDING CODE/LEVEL 2 ALTERATIONS.
  
 3)INTERIOR FINISHES SHALL COMPLY WITH
 FBC SECTION/TABLE 803.5-C AND SHALL MEET
 THE CLASS C FLAMESPREAD CRITERIA.ALL
 CARPETING SHALL COMPLY WITH THE RADIANT
 FLUX REQUIREMENTS.
  
 B)THE SUSPENDED ACOUSTICAL CEILING
 SHALL BE INSTALLED IN ACCORDANCE WITH
 THE PROVISIONS OF ASTM635/636.
  
 4)MEANS OF EGRESS SHALL COMPLY WITH FBC
 SECTION 812.
  
 5)ACCESSIBILITY SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE.
  
  
  
 ANY EXISTING WALL/CEILING PENETRATION
 ARE REQUIRED TO BE FIRE-STOPPED TO
 MAINTAIN THE APPLICABLE RATING OF THE
 ASSEMBLY.SEE EXISTING BUILDING CODE
 SECTION 812.3.1.