| Plan Review Notes For Permit 05120043 |
| Permit Number |
05120043 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-04-11 00:00:00 | *** PROVISO *** | | | | | | 1) AS PER 2004 FBC(M) 602.2.1, MATERIALS | | | EXPOSED WITHIN PLENUMS SHALL BE NON - | | | COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD | | | INDEX OF NOT MORE THAN 25 AND SMOKE - | | | DEVELOPED INDEX OF NOT MORE THAN 50 WHEN | | | TESTED IN ACCORDANCE WITH ASTM E 84. | | | | | | 2) PROVIDE RETURN AIR OPENINGS IN FIRE | | | WALLS. | | | | | | 3) AS PER 2004 FBC(M) 607.5.1 FIRE | | | WALLS. | | | DUCTS AND AIR TRANSFER OPENINGS | | | PERMITTED IN FIRE WALLS IN ACCORDANCE | | | WITH SECTION 705.11 OF THE FLORIDA | | | BUILDING CODE, BUILDING SHALL BE | | | PROTECTED WITH APPROVED FIRE DAMPERS | | | INSTALLED IN ACCORDANCE WITH THEIR | | | LISTING. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729. | | | |
|