2005-12-15 00:00:00*** PROVISO ***
  
 1) AS PER 2004 FBC(M) 602.2.1, MATERIALS
 EXPOSED WITHIN PLENUMS SHALL BE NON -
 COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND SMOKE -
 DEVELOPED INDEX OF NOT MORE THAN 50 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84.
  
 2) PROVIDE RETURN AIR OPENINGS IN FIRE
 WALLS.
  
 3) AS PER 2004 FBC(M) 607.5.1 FIRE
 WALLS.
 DUCTS AND AIR TRANSFER OPENINGS
 PERMITTED IN FIRE WALLS IN ACCORDANCE
 WITH SECTION 705.11 OF THE FLORIDA
 BUILDING CODE, BUILDING SHALL BE
 PROTECTED WITH APPROVED FIRE DAMPERS
 INSTALLED IN ACCORDANCE WITH THEIR
 LISTING.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729.
  
  
  