Plan Review Notes
Plan Review Notes For Permit 05120031
Permit Number 05120031
Review Stop M
Sequence Number 3
Notes
Date Text
2006-05-10 00:00:00*** DENIED ***
 1) AS NOTED IN LAST REVIEW 3-27-06 #2,
 MANUAL J CALCULATIONS FOR SYSTEM TWO
 ARE CALLING FOR 17,566 SENSIBLE BTU'S,
 AND THE MECHANICAL PLANS FOR SYSTEM TWO
 ARE CALLING FOR 26,400 SENSIBLE BTU'S.
 THE PLANS CAN ONLY CALL FOR 20% MORE
 THAN THE MANUAL J CAL'S. PER 2004 FBC
 13-607.1.ABC.1.1, PLEASE CORRECT.
  
 2) MANUAL J CAL'S FOR SYSTEM ONE ARE
 CALLING FOR 13,731 SENSIBLE BTU'S, AND
 THE MECHANICAL PLANS FOR SYSTEM ONEARE
 CALLING FOR 18,000 SENSIBLE BTU'S, AGAIN
 THE PLANS CAN ONLY CALL FOR 20% MORE
 THAN THE MANUAL J CAL'S (THE A/C SYSTEMS
 ON THE PLANS ARE TO LARGE FOR THE HOUSE
 ACCORDING TO YOUR MANUAL J CAL'S) PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;