| Plan Review Notes For Permit 05120031 |
| Permit Number |
05120031 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-05-10 00:00:00 | *** DENIED *** | | | 1) AS NOTED IN LAST REVIEW 3-27-06 #2, | | | MANUAL J CALCULATIONS FOR SYSTEM TWO | | | ARE CALLING FOR 17,566 SENSIBLE BTU'S, | | | AND THE MECHANICAL PLANS FOR SYSTEM TWO | | | ARE CALLING FOR 26,400 SENSIBLE BTU'S. | | | THE PLANS CAN ONLY CALL FOR 20% MORE | | | THAN THE MANUAL J CAL'S. PER 2004 FBC | | | 13-607.1.ABC.1.1, PLEASE CORRECT. | | | | | | 2) MANUAL J CAL'S FOR SYSTEM ONE ARE | | | CALLING FOR 13,731 SENSIBLE BTU'S, AND | | | THE MECHANICAL PLANS FOR SYSTEM ONEARE | | | CALLING FOR 18,000 SENSIBLE BTU'S, AGAIN | | | THE PLANS CAN ONLY CALL FOR 20% MORE | | | THAN THE MANUAL J CAL'S (THE A/C SYSTEMS | | | ON THE PLANS ARE TO LARGE FOR THE HOUSE | | | ACCORDING TO YOUR MANUAL J CAL'S) PLEASE | | | CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|