| Plan Review Notes For Permit 05120031 |
| Permit Number |
05120031 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-03-27 00:00:00 | *** DENIED *** | | | 1) ENERGY CALCULATIONS ARE CALLING FOR | | | 56,000 TOTAL BTU'S, AND THE MECHANICAL | | | PLANS ARE CALLING FOR 60,400 TOTAL | | | BTU'S. THE PLANS CAN NOT CALL FOR MORE | | | TOTAL BTU'S THAN THE ENERGY CAL'S, | | | PLEASE CORRECT. | | | | | | 2) MANUAL J CALCULATIONS FOR SYSTEM TWO | | | ARE CALLING FOR 17,566 SENSIBLE BTU'S, | | | AND THE MECHANICAL PLANS FOR SYSTEM TWO | | | ARE CALLING FOR 26,400 SENSIBLE BTU'S. | | | THE PLANS CAN ONLY CALL FOR 20% MORE | | | THAN THE MANUAL J CAL'S. PER 2004 FBC | | | 13-607.1.ABC.1.1, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|