| 2006-03-23 00:00:00 | ********** PROVISO ************ |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES, DUE TO |
| | CHANGES IN PLANS. |
| | |
| | 1) NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| | FOR AHU #2. SHOWS 10KW HEAT WITH 45A |
| | OCP. 60A MIN. |
| | |
| | 2)NOTE: PLEASE SEE AN "EQUIPMENT |
| | GROUNDING CONDUCTOR" IS NOW BEING SHOWN |
| | FROM METER TO MAIN CIRCUIT BRKR PANEL. |
| | THIS PANEL IS FIRST MEANS OF DISCONNECT |
| | AND THE EQUIP GRND IS ONLY INSTALLED |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | 250.6,250.24B |
| | |
| | 3) NOTE: PLEASE SEE LOCATION OF GFI ON |
| | PENINSULAR SHALL BE VERFIED, AS LOCATION |
| | DOES NOT SEEM TO MEET 210.52C2, (6" OF |
| | COUNTER OVERHANG). |
| | |
| | 4)NOTE: PLANS ARE TO REFERENCE THE 2002 |
| | NFPA-70. |
| | |
| | ************************************** |
| | PLEASE SEE THIS "PROVISO " IS TO REVISE |
| | PLANS , ALONG WITH ANY OTHER REVISIONS |
| | BEFORE ROUGH ELECTRICAL INSPECTION IS |
| | CALLED IN. |
| | IF THERE ARE ANY QUESTIONS , PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | PLEASE SEE "PROVISO", IF PLANS COME BACK |
| | FOR ANY OTHER COMMENTS FROM OTHER |
| | TRADES, PLEASE BE SURE TO MAKE |
| | CORRECTIONS TO "PROVISO" AT THAT TIME. |