| 2005-12-22 00:00:00 | **** UNSAT **** |
| | |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52. PLEASE SEE REDLINED PLANS FOR |
| | LOCATIONS/ |
| | PLEASE ALSO VERIFY THE "LOFT" AREA, AS |
| | IF THE IS CALLED A LOFT/HABITABLE RM, |
| | THEN TWO ADDITIONAL RECEPTS WOULD BE |
| | REQUIRED(SEE REDLINES) IF A HALL, THEN |
| | THIS WOULD BE OK. |
| | |
| | 3)NOTE: PLEASE PROVIDE ONE ADDITIONAL |
| | SD AT THIS SAME "LOFT" AREA OUTSIDE |
| | BEDRMS. |
| | NFPA-72 11.5.1.1 |
| | |
| | 4)NOTE: PLEASE LIST THE MIN REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S) PER |
| | 210.11C3 |
| | PLEASE SEE THIS MUST BE 20A AND #12. |
| | PLEASE SEE BATH RM BETWEEN BEDRMS 3 AND |
| | 4, WHICH SEEMS TO SHOWS GFI, HOWEVER |
| | THIS MUST BE WITHIN 3' OF SINK'S EDGE. |
| | SCALE PUTS THIS CLOSE, PLEASE VERIFY. |
| | |
| | 5)NOTE: PLEASE MAKE REFERENCE TO THE |
| | CURRENT NEC (2002) ON PLANS. |
| | |
| | 6)NOTE: PLEASE CORRLELATE A/C HEAT |
| | STRIPS ON ELECTRICAL PLANS AND A/C |
| | SHEETS. |
| | PLEASE SEE BOTH UNITS SHOW 10KW HEAT ON |
| | MECHANICAL, HOWEVER ONE IS SHOWN AS 5KW |
| | ON PANEL SCHEDUL, YET OCP AND AWG IS |
| | SHOWN FOR 10KW. |
| | |
| | 7)NOTE: PLEASE VERIFY LOAD CALCS, |
| | PERCENTAGES AND KVA IS SHOWN, HOWEVER |
| | THESE DO NOT DETAIL WHAT THEY ARE FROM. |
| | 220.30, 215.5 |
| | |
| | 8) NOTE: PLEASE VERIFY THE RECEPT SHOWN |
| | ON PENINSULAR, AS NEITHER IS SHOWN AS |
| | GFI? |
| | PLEASE VERIFY AS A MIN OF ONE IS |
| | REQUIRED PER 210.52C3, AND GFI PER |
| | 210.8A6 |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | ONE SET OF OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |