Plan Review Notes
Plan Review Notes For Permit 05120031
Permit Number 05120031
Review Stop E
Sequence Number 1
Notes
Date Text
2005-12-22 00:00:00**** UNSAT ****
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52. PLEASE SEE REDLINED PLANS FOR
 LOCATIONS/
 PLEASE ALSO VERIFY THE "LOFT" AREA, AS
 IF THE IS CALLED A LOFT/HABITABLE RM,
 THEN TWO ADDITIONAL RECEPTS WOULD BE
 REQUIRED(SEE REDLINES) IF A HALL, THEN
 THIS WOULD BE OK.
  
 3)NOTE: PLEASE PROVIDE ONE ADDITIONAL
 SD AT THIS SAME "LOFT" AREA OUTSIDE
 BEDRMS.
 NFPA-72 11.5.1.1
  
 4)NOTE: PLEASE LIST THE MIN REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) PER
 210.11C3
 PLEASE SEE THIS MUST BE 20A AND #12.
 PLEASE SEE BATH RM BETWEEN BEDRMS 3 AND
 4, WHICH SEEMS TO SHOWS GFI, HOWEVER
 THIS MUST BE WITHIN 3' OF SINK'S EDGE.
 SCALE PUTS THIS CLOSE, PLEASE VERIFY.
  
 5)NOTE: PLEASE MAKE REFERENCE TO THE
 CURRENT NEC (2002) ON PLANS.
  
 6)NOTE: PLEASE CORRLELATE A/C HEAT
 STRIPS ON ELECTRICAL PLANS AND A/C
 SHEETS.
 PLEASE SEE BOTH UNITS SHOW 10KW HEAT ON
 MECHANICAL, HOWEVER ONE IS SHOWN AS 5KW
 ON PANEL SCHEDUL, YET OCP AND AWG IS
 SHOWN FOR 10KW.
  
 7)NOTE: PLEASE VERIFY LOAD CALCS,
 PERCENTAGES AND KVA IS SHOWN, HOWEVER
 THESE DO NOT DETAIL WHAT THEY ARE FROM.
 220.30, 215.5
  
 8) NOTE: PLEASE VERIFY THE RECEPT SHOWN
 ON PENINSULAR, AS NEITHER IS SHOWN AS
 GFI?
 PLEASE VERIFY AS A MIN OF ONE IS
 REQUIRED PER 210.52C3, AND GFI PER
 210.8A6
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE SET OF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  