| Plan Review Notes For Permit 05120024 |
| Permit Number |
05120024 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-20 00:00:00 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE ON | | | FORM 600A-04 (2004) PER FBC 13.600.3.A . | | | | | | 2) A/C EQUIPMENT ON MECHANICAL PLANS IS | | | TO LARGE (49,400 SEN. BTU'S.). MANUAL J | | | IS CALLING FOR 28,620 SEN. BTU'S + 20% = | | | 34,344 SEN. BTU'S.. PLEASE SEE 2004 FBC | | | 13.607.1.ABC.1.1. | | | | | | 3) NO MECHANICAL DESIGN (DUCT WORK) ON | | | MECHANICAL PLAN (H-1). | | | | | | 4) NEED TO FILE A NOTICE OF | | | COMMENCEMENT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|