| Plan Review Notes For Permit 05120017 |
| Permit Number |
05120017 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-02-03 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PROVIDE A RISER DIAGRAM FOR THE | | | SERVICE, INCLUDE AIC RATING FROM | | | CALCULATION PER 110.9&10. | | | | | | 2} GFI REQUIRED PER: | | | 210.8(A)(2)GARAGES, AND ALSO ACCESSORY | | | BUILDINGS THAT HAVE A FLOOR LOCATED AT | | | OR BELOW GRADE LEVEL NOT INTENDED AS | | | HABITABLE ROOMS AND LIMITED TO STORAGE | | | AREAS, WORK AREAS, AND AREAS OF SIMILAR | | | USE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|