Plan Review Notes
Plan Review Notes For Permit 05120017
Permit Number 05120017
Review Stop E
Sequence Number 2
Notes
Date Text
2006-02-03 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE A RISER DIAGRAM FOR THE
 SERVICE, INCLUDE AIC RATING FROM
 CALCULATION PER 110.9&10.
  
 2} GFI REQUIRED PER:
 210.8(A)(2)GARAGES, AND ALSO ACCESSORY
 BUILDINGS THAT HAVE A FLOOR LOCATED AT
 OR BELOW GRADE LEVEL NOT INTENDED AS
 HABITABLE ROOMS AND LIMITED TO STORAGE
 AREAS, WORK AREAS, AND AREAS OF SIMILAR
 USE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026