| Plan Review Notes For Permit 05120012 |
| Permit Number |
05120012 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-16 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR | | | THE PLAN MUST PRINT AND SIGN THEIR NAME | | | PER 104.2.1 FBC. | | | | | | 2} INDICATE THE SERVICE LOCATION ON THE | | | PLAN. | | | | | | 3} SHOW THE REQUIRED DISCONNECTING MEANS | | | @ THE COTTAGE PER 225.31 AND GROUNDING | | | PER 250.32. | | | | | | 4} PROVIDE THE AIC RATING FOR THE NEW | | | EQUIPMENT IF THE SERVICE IS BEING | | | CHANGED AS THE NOTE IMPLIES. | | | | | | 5} THE LOAD CALCULATION GIVEN IS | | | INCORRECT AS IT DOES NOT INCLUDE THE | | | APPLIANCES IN THE COTTAGE. PLEASE | | | CORRECT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|