| 2008-07-28 15:31:57 | REVISIONS DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT P2.1.1 REVISIONS NOT CLOUDED BY MATCH LINE ALONG |
| | COLUUM LINE 10.--IDENTIFY NEW FIXTURES IN THE |
| | TOILET ROOM. THERE IS NO SANITARY SHOWN TO THESE |
| | FIXTURES. SECTION 106.1.3. |
| | |
| | 2. SHT P2.1.2 MANY REVISIONS/CHANGES ARE NOT INDICATED |
| | WITH A CLOUD NOR REVISION NUMBER.--REVISION 15 |
| | BETWEEN COLUUMS F-H/1-3 DOES NOT INDICATE |
| | CHANGE/REVISION FROM FILE SET OF PLANS. PLEASE |
| | CLARIFY. |
| | |
| | 3. SHT P3.1.1 IDENTIFY NEW FIXTURES IN THE TOILET |
| | ROOMS.--NOT FIXTURES ARE SHOWN WHERE HDF/DF IS |
| | INDICATED. PLEASE SHOW ALL FIXTURES. SECTION 106.1.3. |
| | |
| | 4. SHT P3.1.2 MANY REVISIONS NOT CLOUDED NOR INDICATED |
| | WITH A REVISION NUMBER. SECTION 106.1.3. |
| | |
| | 5. SHT P5.1 MANY REVISIONS ARE NOT CLOUDED NOR |
| | INDICATED WITH A REVISION NUMBER. SECTION 106.1.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |