| Plan Review Notes For Permit 05111207 |
| Permit Number |
05111207 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-11-22 14:34:12 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | 1. SHT GO.O CODE ANALYSIS, FIXTURE COUNT INDICATES 5 | | | DRINKING FOUNTAINS PROVIDED. ONLY 3 DRINKING FOUNTAINS | | | ARE LOCATED. PLEASE CLARIFY. 2 SERVICE SINKS ARE | | | INDICATED AS BEING PROVIDED. ONLY 1 SERVICE SINK IS | | | LOCATED. PLEASE CLARIFY. TABLES 1004.1.2 & TABLE | | | 403.1. | | | | | | 2. SHT P5.1 DOMESTIC WATER ISOMETRIC. THE TWO WATER | | | CLOSETS AND ACCESSIBLE LAV FOR THE MEN'S TOILET ROOM, | | | (102), ARE NOT INDICATED ON THE WATER RISER DIAGRAM. | | | PLEASE CORRELATE THE RISER WITH THE FLOOR PLAN. SECTION | | | 106.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|