| 2006-06-25 00:00:00 | IN ELEC |
| | *** UNSAT 2ND REVIEW *** |
| | |
| | 1) NOTE: PLEASE SEE NOTE #1 FROM |
| | PREVIOUS REVIEW AS PLANS PREVIOUSLY CAME |
| | IN UNDER THE 2001 DESIGN. IT WAS |
| | REQUESTED TO SEE 2004 FBC FOR DESIGN AS |
| | THE CODE HAD CHANGED ON OCT 1ST, 2005 TO |
| | THE NEW CODE. |
| | PLEASE SEE HAVE NOW COME BACK AND |
| | RESPONSE MENTIONS ALL DESIGNS ARE NOW |
| | UNDER THE 2004 FBC. |
| | PLEASE SEE FBC CHAPTER 13 REQUIREMENTS |
| | COULD NOT BE LOCATED IN DESIGN/OR ON |
| | PLANS. |
| | PLEASE PROVIDE WORST CASE VOLTAGE DROP |
| | PER 13-413.1ABC.1 |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND |
| | .1.3 FOR LIGHTING CONTROLS REQUIRED. |
| | PLEASE INDICATE THE NEW SYSTEM BEING |
| | USED, SCHEDULING, OVER-RIDES DEVICES, |
| | LOCATIONS, AND THE TIMES OF OVER-RIDES |
| | DEVICES, DEPENDING ON INSTALLATION AND |
| | TYPE OF DEVICES INSTALLED. |
| | PLEASE SEE13-415.1.ABC.3, |
| | PLEASE SEE 13-415.1.AB.1 FOR MIN |
| | CALCULATIONS FOR LIGHTING LEVELS AND |
| | DENSITIES (LPD)TO BE PROVIDED. |
| | PLEASE SEE 13-415.2.ABC.1, AND SPECIFY |
| | METHOD AND TABLES. (415.2.C.1,415.2.B.1 |
| | |
| | ** THE FOLLWING IS NOT A KAMM CONSULTING |
| | ENG'S COMMENT. |
| | |
| | 2) NOTE: PLEASE SEE LANDSCAPE PLANS AS |
| | THE FIRM "KILDAY AND ASSOCIATES" IS |
| | MISSING THE REQUIRED INFORMATION ON |
| | TITLE BLOCKS AS SET-FORTH IN THE FAC |
| | 61G1-16.004 |
| | PLEASE SEE MISSING THE PRINTED NAME AND |
| | LICENSE NUMBER OF THE LANDSCAPE ARCH. |
| | PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER AS REQUIRED PER FS |
| | 481.319. |
| | |
| | 3) NOTE: PLEASE SEE THE RECORDED NOTICE |
| | OF COMMENCMENT SUBMITTED HAS EXPIRED PER |
| | FS 713.13(2). PLEASE KNOW, IF WORK HAS |
| | NOT COMMENCED WITH IN 90 DAYS OF |
| | RECORDING NOC, THEN THE NOC WILL BECOME |
| | "VOID" AND WILL BE REQUIRED TO BE RE- |
| | RECORDED. PLEASE KNOW, THE NOC IS ONLY |
| | REQUIRED BEFORE PICKING UP PERMIT. |
| | |
| | 4) NOTE: PLEASE BE SURE TO "COMPLETELY |
| | REMOVE" ALL OLD/VOIDED SHEETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. PLEASE |
| | ONLY SUBMIT ONE COPY OF THE OLD/VOIDED |
| | REMOVED SHEETS SEPARATELY FOR REFERENCE. |
| | |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |