| 2006-07-18 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | FROM PREVIOUS REVIEW |
| | |
| | 19.)PRODUCT APPROVALS REQUIRED FOR ALL |
| | COMPONENTS AND CLADDING, INCLUDING THE |
| | EIFS SYSTEM, FAC9B72.FLORIDA STATE OR |
| | LOCAL PRODUCT APPROVALS REQUIRED, |
| | FAC9B72.WWW.FLORIDABUILDING.ORG |
| | PRODUCT APPROVALS ARE TO BE REVIEWED BY |
| | DESIGNER OF RECORD, FBC*106.3.3. |
| | |
| | THE REVIEW MAY BE DONE IN THE FORM OF A |
| | SHOP DRAWING STAMP.THE STATE PRODUCT |
| | APPROVAL IS NOT REQUIRED TO BE ON THE |
| | PLAN. |
| | |
| | A CURRENT FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVAL IS REQUIRED, FAC9B72.IF A |
| | FLORIDA STATE PRODUCT APPROVAL FOR 2004 |
| | CODE IS NOT AVAILABLE FOR ANY OF THE |
| | PRODUCTS, PLEASE ADVISE AND THE NOA WILL |
| | BE REVIEWED FOR CODE COMPLIANCE AND IF |
| | FOUND COMPLIANT, A LOCAL PRODUCT |
| | APPROVAL WILL BE ISSUED. |
| | |
| | THE PLAN REFERS TO FL337.8 FOR THE |
| | OVERHEAD DOOR, BUT THE PRODUCT APPROVAL |
| | SUBMITTED WAS 742. |
| | |
| | THE STANLEY SLIDING DOOR IS NOT APPROVED |
| | WHERE WATER INFILTRATION REQUIREMENTS |
| | ARE NEEDED.THIS IS NOT A CODE |
| | CORRECTION; PLEASE CONFIRM PRODUCT'S |
| | CONFORMITY WITH DESIGN INTENT. |
| | |
| | PRODUCT APPROVALS WERE NOT SUBMITTED FOR |
| | THE METAL DOORS SHOWN ON THE ELEVATIONS. |
| | |
| | AS DISCUSSED ON THE TELEPHONE, |
| | REFERENCES TO SPECIFIC PRODUCTS ON THE |
| | PLAN MAY BE ELIMINATED BY THE ARCHITECT |
| | (INITIALED AND DATED) RATHER THAN |
| | PRINTING NEW SHEETS. |
| | |
| | 22.)ID11.9, THE BREAK ROOM SINK IS TO |
| | BE ACCESSIBLE, FBC11-4.24.THE CABINET |
| | DOORS DO NOT ALLOW THE REQUIRED KNEE |
| | CLEARANCE. |
| | |
| | NEW COMMENTS: |
| | |
| | 28.)THE ENGINEER'S SEAL IS EXPIRED |
| | (SOILS REPORT).IT IS THE WRONG SIZE |
| | AND SAYS "CERTIFICATE" RATHER THAN |
| | "LICENSE".FAC61G15-23. |
| | |
| | 29.) PLEASE PROVIDE THE AREA INCREASE |
| | CALCULATIONS ON THE PLAN FOR ALLOWABLE |
| | AREA, SHEET G0.0. |
| | |
| | 30.)CLOUD ALL CHANGES.WHEN |
| | RESUBMITTING, SUBMIT OLD SHEETS |
| | SEPARATELY FOR REFERENCE. |
| | |
| | 31.)ADJACENT ACCESSIBLE PARKING IS TO |
| | BE DISPERSED ACCORDING TO 11-4.6.2 (EXIT |
| | 12). |
| | |
| | 32.)SEE ATTACHED FS553.A 4X PLAN |
| | REVIEW IS REQUIRED TO BE CHARGED IF THE |
| | COMMENTS ARE NOT ADDRESSED A THIRD TIME. |