| 2008-12-08 09:11:36 | ** DENIED REVIEW OF REVISIONS ** |
| | |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT COMPLETE ELECTRICAL PLANS FOR |
| | ALL REVISED WORK AND SYSTEM. RESPONSE LETTER TO |
| | PREVIOUS REVISIONS WHICH HAD COMMENTS STATES SEE NEW |
| | PAGE E6.2 HOWEVER NO E6.2 IS IN ANY OF THE THREE SETS |
| | SUBMITTED. |
| | IN ORDER TO REVIEW CIRCUITING FOR NEW ITEMS ALONG WITH |
| | LOADS, PANEL, ETC PLEASE SUBMIT. THIS AFFECTS THE |
| | ENTIRE SET OF PLANS. |
| | 240.4,310.16,408.4, 408.36 ETC |
| | FBC 106.1.1 FOR CLARITY, COORDINATION OF RECORD PLANS. |
| | THIS ADDITION OF THIS NEW PANEL WAS NOT ON PREVIOUS |
| | REVISIONS SUBMITTED. |
| | |
| | 2) NOTE: PLEASE BE SURE THE LOADS ON RISER SHEET E5.1 |
| | FOR MAIN #2 COORDINATE WITH THE DPA SCHEDULE ON E6.1. |
| | 220. |
| | FBC 106.1.1 |
| | |
| | 3) NOTE: ENERGY CALCULATIONS NOT STAMPED AT THIS TIME. |
| | THERE ARE OPEN PERMITS WITH NEW LIGHTING ON THE |
| | EXTERIOR OF BUILDING AND PARKING AREAS WHICH ARE FED |
| | FROM THIS ELECTRICAL SERVICE WHICH IS NOW NEW. THE |
| | RISER COTNAINS SEVERAL SUB PANELS FOR EXTERIOR SITE |
| | LIGHTING YET NONE ARE LOCATED IN THE INPUT DATA REPORT. |
| | PLEASE BE SURE THE CALCULATIONS ARE REVISED |
| | ACCORDINGLY. |
| | 13-415.2,13-415.2.ABC.1.3, 13-400.3.A |
| | ** PLEASE ALSO KNOW THERE ARE OTHER ITEMS ON THE IDR |
| | WHICH ARE BLANK FOR COMPONENTS WHICH ARE REQUIRED TO BE |
| | PART OF THE *WHOLE BUILDING METHOD*. |
| | PLEASE LOOK FOR COMMENTS FROM OTHER TRADES ON REVIEW OF |
| | CALCULATIONS. |
| | ** ONE EXAMPLE OF OTHER SYSTEMS IS THE IDR DO NOT |
| | INDICATE ANY FLOORS? THERE ARE OTHERS. |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |