| 2009-03-11 13:43:41 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | A. NOTE: AS INDICATED PREVIOUSLY, TURN OFF ALL |
| | PREVIOUSLY APPROVED REVISION CLOUDS AND REVISION |
| | NUMBERS. THIS ADDS MUCH TIME TO THE REVIEW PROCESS AND |
| | CONFUSES THE REVIEW PROCESS AS SOME NEW REVISIONS ARE |
| | NOT APPARENT AND SOME REVISIONS SHOW A CLOUD AND A |
| | REVISIONS NUMBER BUT NO APPARENT REVISION IS SHOWN. |
| | ONLY SHOW THE NEW REVISION CLOUDS AND REVISIONS NUMBERS |
| | FOR REVISIONS BEING CHANGED ON THIS SUBMITTAL. PLEASE |
| | TURN OFF ALL PREVIOUS REVISIONS. SECTION 106.1.3. |
| | |
| | 1. SHT P2.1.1 SHOWS 4 DRINKING FOUNTAINS, BUT ONLY ONE |
| | ACCESSIBLE DRINKING FOUNTAIN. PER SECTION 11-4.1(10)(B) |
| | 50% OF ALL PROVIDED DRINKING FOUNTAINS SHALL BE |
| | ACCESSIBLE. PLEASE INDICATE THE TWO REQUIRED DRINKING |
| | FOUNTAINS. |
| | |
| | 2. SHT P2.1.1 REVISION 16B WAS NOT FOUND ON THE FLOOR |
| | PLAN. PLEASE CORRELATE. -- THE PIPING TO THE 3 LAVS IN |
| | THE WOMENS TOILET ROOM HAS BEEN REVISED WITH NO CLOUD |
| | OR REVISION NUMBER. PLEASE SHOW CLOUDS AND REVISION |
| | NUMBERS FOR ALL REVISIONS SUBMITTED. SECTION 106.1.3. |
| | |
| | 3. SHT P2.1.2 PLANS ARE NOT LEGIBLE BETWEEN COL. LINES |
| | 10-11/F-O. ALSO MANY REVISION NUMBER 16'S SHOWN ON THE |
| | FLOOR PLAN ARE NOT INDICATED IN THE REVISION INDEX. |
| | SOME REVISIONS 16B & 17 SHOW NO CHANGES TO THE |
| | PLUMBING. PLEASE CLARIFY. SECTIONS 106.1.2 & 106.1.3. |
| | |
| | 4. SHT P3.1.1 SHOWS 2 REVISION NUMBER 5 THAT WERE NOT |
| | ON PREVIOUS REVISION SHEET SIGNED, SEALED ON JULY 28, |
| | 2008. IF THESE ARE NEW REVISION THEN NEW REVISION |
| | NUMBERS ARE REQUIRED. SECTION 106.1.3. -- REVISION |
| | NUMBER 17 AT ROOM 104 SHOWS NO PLUMBING REVISION. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 5. SHT P3.1.2 NO CHANGES WERE FOUND WITHIN THE CLOUDS |
| | FOR REVISIONS 16/16B/17. PLEASE CLARIFY. SECTIONS |
| | 106.1.1 & 106.1.3. |
| | |
| | 6. SHT P5.1 MANY REVISION NUMBERS SHOW NO |
| | CHANGE/REVISION TO THE PLANS WITHIN THE CLOUDED AREA. |
| | PLEASE CLARIFY WHAT IS REVISED IN EACH CLOUDED AREA. |
| | SECTION 106.1.1. REVISION 17 SHOWS A CAPPED HUB DRAIN. |
| | PER SECTION 704.5 DEAD ENDS ARE PROHIBITED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |