| 2008-07-31 15:43:58 | |
| | |
| | |
| | |
| | |
| | ** DENIEDREVIEW ** |
| | |
| | 1) NOTE: PLEASE VERIFY LOCATION AND TYPE OF DEVICE FOR |
| | G2 FIXTURES IN AREA BETWEEN *WRITE-UPS* AND SERVICE |
| | DRIVE. |
| | THIS ACCENT LIGHTING SHOWS CONTROL BY WHAT APPEARS TO |
| | BE A STANDARD SINGLE POLE SWITCH BASED ON LEGEND |
| | ALTHOUGH THE NOTE MENTIONS OFFICE LIGHTING. IF THIS IS |
| | AN OCCUPANCY SENSOR HOW WOULD THE LOCATION OF THIS |
| | DEVICE INSIDE THE OFFICE WORK FOR THE LIGHTING |
| | OUTSIDE? |
| | PLEASE SEE OTHER AREA AS HALLWAY OUTSIDE RORY'S OFFICE |
| | WHICH SHOWS STANDARD THREE WAY SWITCH. |
| | 13-415.1.ABC.1.1,.1.2,1.3. |
| | |
| | 2) NOTE: PLEASE GO OVER ENERGY CALCULATIONS AS THERE |
| | ARE FIXTURES ON PLANS WHICH ARE NOT IN THE INPUT DATA |
| | REPORT. |
| | 13-415.2, 13-415.2.ABC.1.1, .1.2. |
| | |
| | 3) NOTE: PANEL SCHEDULES NEED TO BE REVISED TO SPECIFIC |
| | ROOMS AND AREAS IN WHICH THEY FEED. |
| | NEC 408.4. |
| | QUOTING *LIGHTING* OR *RECEPTACLES* IS NOT ACCEPTABLE. |
| | FBC 106.5, 106.1.1, 106.3.5.1.2 |
| | |
| | |
| | |
| | ** THERE ARE STILL COMMENTS FROM PREVIOUS REVIEW. |
| | |
| | ** IF THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE |
| | NOT CLEAR IN ANY MANOR PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | |
| | |
| | IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |