| 2006-02-03 00:00:00 | DENIED:2004 FLORIDA BUILDING CODE |
| | |
| | 1.PLAN SHEET M2.1.2, 16 X 14 RETURN |
| | AIR DUCT INTO LOCKER ROOM #145 |
| | PENETRATES RATED RATED WALL BETWEEN THE |
| | LOCKER ROOM & SERVICE CENTER, NO FIRE |
| | DAMPER IS INDICATED.PLEASE CLARIFY. |
| | |
| | 2.EQUIPMENT SCHEDULE INDICATES RTU 14 |
| | & 15 (SERVICE GARAGE).THE EQUIPMENT |
| | SCHEDULE INDICATES A TOTAL OF OUTSIDE |
| | AIR 1040 CFM.PER 2004 FMC 404.2 |
| | MINIMUM VENTILATION SHALL BE .05 CFM PER |
| | SQAURE FOOT & THE SYSTEM SHALL BE |
| | CAPABLE OF PRODUCING A VENTILATION RATE |
| | OF 1.5 CFM PER SQUARE FOOT. |
| | |
| | 3.PLAN SHEET M2.2.2, PLEASE CLARIFY |
| | THE 'VEHICLE EXTRACTION SYSTEM FAN BY |
| | OTHERS'.WILL THIS HOOK-UP TO THE |
| | INDIVIDUAL MUFFLER EXHAUST? |
| | |
| | 4.PLAN SHEET M8.1 SEQUENCE OF |
| | OPERATION ITEM 4 INDICATES THE GARAGE |
| | DOORS WILL BE NORMALLY CLOSED.IS THIS |
| | CORRECT? |
| | |
| | 5.RTU-14 & RTU-15 WILL BE |
| | RECIRCULATING AIR FROM THE SERVICE AREA. |
| | PLEASE SHOW COMPLIANCE WITH 2004 FBC |
| | 406.6. |
| | |
| | 6.PLEASE CLARIFY IF THE ALARMS FOR THE |
| | CO & FV SENSORS ARE TIED TO THE FIRE |
| | ALARM. |
| | |
| | 7.PLEASE PROVIDE SUBMITTAL FOR THE |
| | FLAMMABLE VAPOR SENSOR & THE CARBON |
| | MONOXIDE SENSOR.PLEASE NOTE, TESTING |
| | OF SENSORS REQUIRED FOR FINAL |
| | INSPECTION. |
| | |