| 2006-01-10 00:00:00 | ******DENIED****** |
| | |
| | 1) PLEASE SHOW ALL HYDRANT LOCATIONS ON |
| | OKEECHOBEE BLVD OR SOUTH OF THE |
| | PROPERTY. |
| | |
| | 2) PLEASE PROVIDE INFORMATION FOR GATE |
| | CONTROL DEVICES AND INDICATE FAIL SAFE |
| | OPERATION IN EVENT OF POWER FAILURE. |
| | |
| | 3) CONSTRUCTION, ALTERATION AND |
| | DEMOLITION TO COMPLY WITH NFPA 241. |
| | |
| | 4) PLEASE INDICATE THE INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILINGS IN |
| | TERM OF CLASS A, B, OR C. |
| | |
| | 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENTS FOR HANDRAILS AND GUARDS. |
| | |
| | 6) AN ADDRESS IS REQUIRED ON BUILDING |
| | AND SHALL BE A MINIMUM OF 6" IN HEIGHT |
| | AND CONTRASTING WITH THE BACKGROUND. |
| | |
| | 7) PLEASE PROVIDE MANUFACTURER SPEC |
| | SHEETS REGARDING FIRE RESISTANCE FOR |
| | PROPOSED CANOPY. |
| | |
| | 8) THE MIDDLE EXIT DOOR ON THE EAST SIDE |
| | OF THE SERVICE CENTER SHOWS EQUIPMENT IN |
| | FRONT OF IT THAT WOULD APPEAR TO BE AN |
| | OBSTRUCTION FOR EXITING. |
| | |
| | 9) A KNOX BOX IS REQUIRED ON BUILDING. |
| | |
| | 10) DUCT SMOKE DETECTORS SHALL INITIATE |
| | A GENERAL FIRE ALARM IN ACCORDANCE WITH |
| | LOCAL REQUIREMENTS. |
| | |
| | 11) AS PLANS INDICATE, SEPARATE SHOP |
| | DRAWINGS AND PERMITS ARE REQUIRED FOR |
| | FIRE SPRINKLER AND FIRE ALARM SYSTEMS. |
| | |
| | 12) FIRE EXTIGUISHERS TO BE MOUNTED AT |
| | DISTANCES TO SATISFY THE 75' TRAVEL |
| | DISTANCE REQUIREMENT. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLANS REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |