| 2006-03-16 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED.THE NOC PROVIDED |
| | DOES NOT HAVE THE RECORDING STAMP |
| | SHOWING BOOK AND PAGE. |
| | |
| | 2.)ENERGY CALCS ARE TO BE SIGNED AND |
| | SEALED, FBC13-103.1.1.1. |
| | |
| | 3.)ENERGY CALCS TO BE SIGNED IN THE |
| | OWNER/AGENT LINE FBC13-103.1. |
| | |
| | 4.)THE ENGINEERING CALCULATIONS |
| | PREPARED BY TLC ARE TO INCLUDE THE CA |
| | NUMBER, FAC61G15-23.002. |
| | |
| | 5.)ENGINEERING CALCULATIONS ARE TO BE |
| | SIGNED AND SEALED ON EACH SHEET OR TO |
| | HAVE AN INDEX SHEET, FAC61G15-23-002. |
| | THIS HAS BEEN DISCUSSED WITH FBPE; |
| | PLEASE CONTACT THEM IF YOU NEED |
| | CLARIFICATION. |
| | |
| | 6.)THE STRESS INCREASE SHOWN ON SHEET |
| | 11 OF 49 IN THE STRUCTURAL CALCS IS NOT |
| | PERMITTED, FBC1605.3.1.1(2). |
| | |
| | 7.)SHEET 32 OF 49 OF THE STRUCTURAL |
| | CALCS REFER TO ASCE7 98, SHOULD BE ASCE7 |
| | 02, FBC35. |
| | |
| | 8.)SHEET G0.0 DECLARES THE STORAGE AND |
| | AUTO REPAIR AREA AS S1 NON SEPARATED |
| | USES.SEE FBC302.1.1, INCIDENTAL USES |
| | SHALL BE CLASSIFIED IN ACCORDANCE WITH |
| | THE MAIN OCCUPANCY OR SEPARATED FBC |
| | TABLE 302.1.1, OR MIXED OCCUPANCY FBC |
| | TABLE 302.3.2. |
| | |
| | 9.)PLANS SHOW A 2 HOUR SEPARATION |
| | BETWEEN THE S1 AND B AREAS, FBC TABLE |
| | 302.3.2 REQUIRES 3 HOUR. |
| | |
| | 10.)PROVIDE AREA CALCULATIONS ON SHEET |
| | G0.00; EXISTING SF, DEMO SF, ADDITION, |
| | NEW TOTAL.THIS SHOULD BE DONE PRIOR TO |
| | IMPACT FEE ASSESSMENT. |
| | |
| | 11.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 12.)SHEET A2.0B, NO EXIT LIGHT SHOWN |
| | AT EXIT 5. |
| | |
| | 13.)ACCESSIBLE PARKING IS TO COMPLY |
| | WITH CITY OF WEST PALM BEACH STANDARD, |
| | SEE ATTACHED. |
| | |
| | 14.)FIRST FLOOR LIFE SAFETY PLAN SHOWS |
| | THE PATH OF TRAVEL FROM PARTS INVENTORY |
| | LEADING TO EXIT 9.THIS SHOULD BE |
| | MEASURED TO AN ACCESSIBLE EXIT (EXIT 9 |
| | SHOWS A STEP), FBC11-4.13(9).WHEN |
| | MEASURED FROM FARTHER AWAY FROM THE |
| | POINT SHOWN ON THE PLAN TO EXIT 7, THE |
| | DISTANCE APPEARS GREATER THAN THE 200FT |
| | ALLOWED. |
| | |
| | 15.)THE SECOND FLOOR IS REFERRED TO AS |
| | BOTH A SECOND FLOOR AND A MEZZANINE. |
| | FBC505, IS THIS A MEZZANINE OR A SECOND |
| | FLOOR? |
| | |
| | 16.)IS THE COVERED OPEN AREA BETWEEN |
| | THE TWO EXISTING BUILDINGS INCLUDED IN |
| | THE BUILDING AREA?SEE FBC CHAPTER 2, |
| | DEFINITION OF BUILDING AREA. |
| | |
| | 17.)DECLARE AN OCCUPANCY FOR THE OPEN |
| | AREA, FBC406.SHOW REQUIRED OCCUPANCY |
| | SEPARATION. |
| | |
| | 18.)PROVIDE A SOILS INVESTIGATION |
| | REPORT, FBC1802.2.1. |
| | |
| | 19.)PRODUCT APPROVALS REQUIRED FOR ALL |
| | COMPONENTS AND CLADDING, INCLUDING THE |
| | EIFS SYSTEM, FAC9B72.FLORIDA STATE OR |
| | LOCAL PRODUCT APPROVALS REQUIRED, |
| | FAC9B72.WWW.FLORIDABUILDING.ORG |
| | PRODUCT APPROVALS ARE TO BE REVIEWED BY |
| | DESIGNER OF RECORD, FBC*106.3.3. |
| | |
| | 20.)FA6.0 REFERS TO A CODE FROM |
| | FBC2001, REGARDING SIGNAGE.PLEASE |
| | REVISE. |
| | |
| | 21.)CA6.0 DOES NOT SPECIFY THE 2 HOUR |
| | UL LISTED BLOCK REQUIRED IN THE |
| | ASSEMBLY.CHECK ALL UL DETAILS. |
| | FAILURE TO DO SO WILL RESULT IN THE |
| | PLANS BEING FAILED IF THEY ARE SUBMITTED |
| | WITH INCORRECT INFORMATION ON OTHER |
| | ASSEMBLIES. |
| | |
| | 22.)ID11.9, THE BREAK ROOM SINK IS TO |
| | BE ACCESSIBLE, FBC11-4.24. |
| | |
| | 23.)PROVIDE DESIGN CRITERIA FOR |
| | INTERIOR FINISHES, FBC TABLE 803.5. |
| | |
| | 24.)S1.1 REFERS TO ASCE7-98, SHOULD BE |
| | ASCE7-02, FBC35. |
| | |
| | 25.)M01 REFERS TO FBC2001, SPECIAL |
| | NOTES. |
| | |
| | 26.)M7.1 REFERS TO FBC2001.CLEARANCE |
| | FOR MECHANICAL EQUIPMENT IS TO COMPLY |
| | WITH FBC1509.7. |
| | |
| | 27.) M7.1 DETAIL 6 SHOWS WOOD BLOCKING. |
| | NONCOMBUSTIBLE ONLY ALLOWED, FBC CHAPTER |
| | 6. |
| | |
| | |