| 2005-12-01 00:00:00 | 1) THIS ROOF IS MISSING OR NOT IN |
| | COMPLIANCE WITH THE FOLLOW ITEMS: |
| | |
| | _X__ CONTRACTOR DID NOT PROVIDE THE MEAN |
| | ROOF HEIGHT. |
| | |
| | _X__ CONTRACTOR DID NOT INDICATE THE |
| | ROOF PITCH. |
| | |
| | __X_ CONTRACTOR FAILED TO INDICATE WHICH |
| | SYSTEM TO BE USED. |
| | |
| | _X__ THE SYSTEM PROVIDED HAS A LOW |
| | PRESSURE FOR ZONE ___ . |
| | |
| | _X__ THE SYSTEM PROVIDED STATES |
| | LIMITATION# 7, SHOULD THE FASTENER |
| | RESISTANCE BE LESS THAN THAT |
| | REQUIRED, AS DETERMINED BY THE |
| | BUILDING OFFICIAL, A REVISED |
| | FASTENER SPACING, PREPARED , SIGNED |
| | AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF |
| | CONSULTANT MAY BE SUBMITTED. |
| | |
| | _X__THE SYSTEM PROVIDED INDICATES |
| | LIMITATION# 9, NO ENHANCED |
| | FASTENING ALLOWED. |
| | |
| | 2) FBC 1606.2.5THE SYSTEM SELECTED |
| | FROM THE SUBMITTED FLAT ROOF PRODUCT |
| | APPROVAL NOA HAS A MAXIMUM DESIGN |
| | PRESSURE OF LESS THAN -89 PSF AND CITES |
| | GENERAL LIMITATION #9 (SEE PAGE 9 |
| | OF_18).GENERAL LIMITATION #9 PROHIBITS |
| | RATIONAL ANALYSIS OR EXTRAPOLATION TO |
| | ENHANCE THE UPLIFT PRESSURE AT PERIMETER |
| | AND CORNER AREAS BY REDUCING THE |
| | FASTENER SPACING IN THESE AREAS.EITHER |
| | SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT |
| | APPROVAL) THAT DOES NOT CITE GENERAL |
| | LIMITATION #9.ALTERNATIVELY IF THE |
| | SELECTED SYSTEM DOES CITE GENERAL |
| | LIMITATION #9, IT MUST HAVE A MAXIMUM |
| | DESIGN PRESSURE THAT EXCEEDS THE |
| | PRESSURE IN ROOF ZONE 3 (TYPICALLY -89 |
| | PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR |
| | LESS). |
| | |
| | 3) 713.13 F.S.A NOTICE OF COMMENCEMENT |
| | SHALL BE RECORDED AT PALM BEACH COUNTY |
| | COURTHOUSE AND A COPY SUBMITTED TO THIS |
| | OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| | BLANK FORMS ARE AVAILABLE FROM THIS |
| | OFFICE. |
| | NOTE: THE NOTICE OF COMMENCEMENT MUST BE |
| | RE-RECORDED IF THE DESCRIBED IMPROVEMENT |
| | OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| | 90 DAYS OF RECORDING. |
| | |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | TEL: (561) 805-6726 |
| | FAX: (561) 659-8026 |