| 2005-12-29 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- ALL PLANS SUBMITTED AFTER OCTOBER 1ST |
| | 2005 ARE REQUIRED TO COMPLY WITH FBC |
| | 2004. REVISE ALL PLANS, GENERAL NOTES, |
| | DESIGN PARAMETERS, CONSTRUCTION TYPE AND |
| | ALL PERTINENT ITEMS SHOWN ON PLANS AS |
| | REQUIRED TO COMPLY WITH FBC 2004. |
| | |
| | 2- TRUSS DESIGN DRAWINGS NEED TO BE |
| | PROVIDED TO THE BUILDING OFFICIAL FOR |
| | APPROVAL PRIOR TO INSTALLATION. SEC. |
| | R802.10.1 RESIDENTIAL FBC 2004. |
| | (REMAINDER: DESIGNER OF RECORD TO REVIEW |
| | ALL TRUSSES PRIOR TO SUBMITTAL TO THIS |
| | OFFICE). |
| | |
| | 3- DESIGNER OF RECORD TO REVIEW ALL |
| | PRODUCT APPROVALS PRIOR TO SUBMITTAL TO |
| | THIS OFFICE AS REQUIRED BY SEC. 106.3.3 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 4- PROVIDE ALL INFORMATION ON PLANS |
| | REGARDING THE SEPARATION AND OPENING |
| | PROTECTION AS REQUIRED BY SEC. R309 OF |
| | RESIDENTIAL FBC 2004. |
| | |
| | 5- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 6- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: |
| | A) TRUSS CONNECTORS SPECIFIED ON |
| | PLANS. PROVIDE ONLY THE COVER PAGE AND |
| | PAGES SHOWING THE SPECIFIC CONNECTOR |
| | SPECIFIED ON PLANS. PLEASE DON'T SUBMIT |
| | COMPLETE REPORT TO EXPEDITE REVIEW |
| | PROCESS AND SAVE PAPER. |
| | |
| | B) GARAGE DOORS: FLORIDA NUMBER |
| | SUBMITTED IS NOT LONGER LISTED. |
| | |
| | C) 2" WINDOW MULLION: NEED CURRENT |
| | DADE COUNTY NOA THAT MATCHES ONE |
| | SUBMITTED FOR FLORIDA APPROVAL. |
| | |
| | D) FIXED WINDOWS: MISSING FLORIDA |
| | PRODUCT APPROVAL. |
| | |
| | E) ATRIUM DOOR: SEE PLANS FOR SIZE AND |
| | DOOR SWING DIRECTION. |
| | |
| | 7- SOIL TEST REPORT WAS DONE BASED ON |
| | FBC 2001. NEED CURRENT SOIL TEST REPORT |
| | COMPLYING WITH FBC 2004. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |