| Plan Review Notes For Permit 05111170 |
| Permit Number |
05111170 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-05 00:00:00 | DENIED; | | | 1.RISER DIAGRAM DOES NOT MATCH FLOOR | | | PLAN. FLOOR PLAN ONLY HAS 2- TOILETS AND | | | 2-LAVS. RISER DIAGRAM HAS 3- W/C"S AND | | | 3-LAVS. BRANCH DRAIN FOR W/M TO BE 3" | | | SEE SEC. 406.3 | | | ONE SET OF PANS MARKED IN RED . | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|