| 2006-06-08 00:00:00 | |
| | |
| | DENIED |
| | |
| | PREVIOUS COMMENTS WERE NOT ADDRESSED |
| | |
| | 3) SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| | COMPLY WITH R802.10.1 FBC. SHALL BE |
| | SUBMITTED PRIOR TO TRUSS INSTALLATION |
| | ***WHEN ENGINEERED TRUSS DRAWINGS ARE |
| | SUBMITTED THEY SHALL BE SIGNED AND |
| | SEALED BY THE ENGINEER OF RECORD, THIS |
| | IS USUALLY DONE AFTER ORDERING THE |
| | TRUSSES AND SHALL BE SUBMITTED TO THE |
| | BUILDING DEPT. FOR APPROVAL BEFORE THE |
| | TRUSSES AREINSTALLED.*** |
| | |
| | 4) PROVIDE ATTIC ACCESS PER R807 FBC |
| | ***THE LOCATION OF ATTIC ACCESS IS IN |
| | THE FLAT ROOF AREA, PLEASE INSTALL IN |
| | CEILING THAT HAS ATTIC ABOVE.*** |
| | |
| | 8) TWO DIFFERENT PRODUCT APPROVALS WERE |
| | SUBMITTED FOR DOORS CHOOSE THE PRODUCT |
| | THAT WILL BE USED FOR SUBMITTAL AND |
| | REMOVE WHAT WILL NOT BE USED*** BOTH |
| | PRODUCT APPROVALS WERE REMOVED FROM |
| | SUBMITTAL, PLEASE RESUBMIT DOOR PRODUCT |
| | APPROVAL THAT WILL BE USED(2 COPIES)*** |
| | |
| | 9) ENERGY CALC'S SHALL BE SIGNED AND |
| | DATED OWNER/AGENT*** PLEASE SEE BOTTOM |
| | OF ENERGY CALC'S THEY NEED TO BE SIGNED |
| | AND DATED BY OWNER. ALSO THEY MUST BE |
| | DONE ON UPDATED FORM 600C-04.*** |
| | |
| | 10) CHANGE DRAWINGS TO REFLECT CURRENT |
| | 2004 FBC AND MWF TABLE 1609.6A AND |
| | COMPONENTS & CLADDING TABLE 1609.6B |
| | *** HAS NOT BEEN RECTIFIED*** |
| | |
| | 11) DRAWING SHT 1/6 AND 4/6 SHOW BLOCK |
| | WALL AT ROOF TRANSITION WHILE SHT 2/6 |
| | SHOWS WOOD BEARING WALL, PLEASE CLARIFY |
| | ALSO CORRECT THE SIMPSON TIE STRAP |
| | ACCORDINLY. *** WHITEOUT IS NOT |
| | ACCEPTABLE ON THE CONSTRUCTION DOCUMENTS |
| | PLEASE SEE THAT 4/6 STILL SHOWS A BLOCK |
| | WALL AND 2/6 SHOWS WOOD*** |
| | |
| | |
| | NOTE: FBC = FLORIDA BUILDING CODE 2004 |
| | FBC* = WEST PALM BEACH |
| | ADMINISTATIVE AMMENDMENTS TO FBC |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | |
| | |
| | |