Plan Review Notes
Plan Review Notes For Permit 05111170
Permit Number 05111170
Review Stop B
Sequence Number 2
Notes
Date Text
2006-06-08 00:00:00 
  
 DENIED
  
 PREVIOUS COMMENTS WERE NOT ADDRESSED
  
 3) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC. SHALL BE
 SUBMITTED PRIOR TO TRUSS INSTALLATION
 ***WHEN ENGINEERED TRUSS DRAWINGS ARE
 SUBMITTED THEY SHALL BE SIGNED AND
 SEALED BY THE ENGINEER OF RECORD, THIS
 IS USUALLY DONE AFTER ORDERING THE
 TRUSSES AND SHALL BE SUBMITTED TO THE
 BUILDING DEPT. FOR APPROVAL BEFORE THE
 TRUSSES AREINSTALLED.***
  
 4) PROVIDE ATTIC ACCESS PER R807 FBC
 ***THE LOCATION OF ATTIC ACCESS IS IN
 THE FLAT ROOF AREA, PLEASE INSTALL IN
 CEILING THAT HAS ATTIC ABOVE.***
  
 8) TWO DIFFERENT PRODUCT APPROVALS WERE
 SUBMITTED FOR DOORS CHOOSE THE PRODUCT
 THAT WILL BE USED FOR SUBMITTAL AND
 REMOVE WHAT WILL NOT BE USED*** BOTH
 PRODUCT APPROVALS WERE REMOVED FROM
 SUBMITTAL, PLEASE RESUBMIT DOOR PRODUCT
 APPROVAL THAT WILL BE USED(2 COPIES)***
  
 9) ENERGY CALC'S SHALL BE SIGNED AND
 DATED OWNER/AGENT*** PLEASE SEE BOTTOM
 OF ENERGY CALC'S THEY NEED TO BE SIGNED
 AND DATED BY OWNER. ALSO THEY MUST BE
 DONE ON UPDATED FORM 600C-04.***
  
 10) CHANGE DRAWINGS TO REFLECT CURRENT
 2004 FBC AND MWF TABLE 1609.6A AND
 COMPONENTS & CLADDING TABLE 1609.6B
 *** HAS NOT BEEN RECTIFIED***
  
 11) DRAWING SHT 1/6 AND 4/6 SHOW BLOCK
 WALL AT ROOF TRANSITION WHILE SHT 2/6
 SHOWS WOOD BEARING WALL, PLEASE CLARIFY
 ALSO CORRECT THE SIMPSON TIE STRAP
 ACCORDINLY. *** WHITEOUT IS NOT
 ACCEPTABLE ON THE CONSTRUCTION DOCUMENTS
 PLEASE SEE THAT 4/6 STILL SHOWS A BLOCK
 WALL AND 2/6 SHOWS WOOD***
  
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004
 FBC* = WEST PALM BEACH
 ADMINISTATIVE AMMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
  
  
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  