Plan Review Notes
Plan Review Notes For Permit 05111159
Permit Number 05111159
Review Stop E
Sequence Number 4
Notes
Date Text
2006-06-21 00:00:00********* UNSAT ***********
  
 1) NOTE: PLEASE SEE PANELS AS SHOWN ON
 PLANS E1.1 DO NOT CORRELATE WITH RISER
 AND PANEL SCHEDULES.
 PLEASE SEE TWO PANEL "A"'S SHOWN, 1-400A
 AND 1-200A. PLEASE SEE PANEL "B" WHICH
 IS SHOWN AS 600A'S ON PLANS AND 200A'S
  
 2) NOTE: PLEASE SEE RISER DIAGRAM
 INDICATES TWO MDP'S AND ONE OF THE
 SCHEDULES INDICATES MDB. IS THIS ONE OF
 THE MDP'S?
 PLEASE ALSO SEE THE 2ND MDP WHICH IS
 400A RATEDSEEMS TO BE FED FROM MDP
 ONE, WHICH IS 600A'S AND DOES NOT
 INDICATE ANY OCP FEEDING THE MDP-2??
 PLEASE VERIFY IF THIS IS A FEED THUR
 LUGS , TAPPED CONDUCTOS ETC.
 PLEASE KNOW, IF TAPPED ? THEN PLEASE SEE
 240.21. PLEASE KNOW, AS SHOWN IS SEEMS
 THE MDP-2 WOULD REQUIRE AND MCB TO LIMIT
 THE LOAD AND FOR PROTECTION OF WHAT IS
 NOW SHOWN AS A MLO MDP.
 PLEASE SEE NO CONDUCTORS ARE BEING
 INDICATED FOR THE EXISTING MDP ETC.
 UNABLE TO VERIFY AT THIS TIME.
 PLEASE SEE 230.70,230.2,230.71,230.72,
 240.4,310.16,240.21 ETC.
 215.5
  
 3) NOTE: PLEASE CLARIFY THE DIFFERENCE
 IN E2.1 AND 2.2.
  
  
 ** PLEASE BE SURE TO REVMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  