| 2006-06-21 00:00:00 | ********* UNSAT *********** |
| | |
| | 1) NOTE: PLEASE SEE PANELS AS SHOWN ON |
| | PLANS E1.1 DO NOT CORRELATE WITH RISER |
| | AND PANEL SCHEDULES. |
| | PLEASE SEE TWO PANEL "A"'S SHOWN, 1-400A |
| | AND 1-200A. PLEASE SEE PANEL "B" WHICH |
| | IS SHOWN AS 600A'S ON PLANS AND 200A'S |
| | |
| | 2) NOTE: PLEASE SEE RISER DIAGRAM |
| | INDICATES TWO MDP'S AND ONE OF THE |
| | SCHEDULES INDICATES MDB. IS THIS ONE OF |
| | THE MDP'S? |
| | PLEASE ALSO SEE THE 2ND MDP WHICH IS |
| | 400A RATEDSEEMS TO BE FED FROM MDP |
| | ONE, WHICH IS 600A'S AND DOES NOT |
| | INDICATE ANY OCP FEEDING THE MDP-2?? |
| | PLEASE VERIFY IF THIS IS A FEED THUR |
| | LUGS , TAPPED CONDUCTOS ETC. |
| | PLEASE KNOW, IF TAPPED ? THEN PLEASE SEE |
| | 240.21. PLEASE KNOW, AS SHOWN IS SEEMS |
| | THE MDP-2 WOULD REQUIRE AND MCB TO LIMIT |
| | THE LOAD AND FOR PROTECTION OF WHAT IS |
| | NOW SHOWN AS A MLO MDP. |
| | PLEASE SEE NO CONDUCTORS ARE BEING |
| | INDICATED FOR THE EXISTING MDP ETC. |
| | UNABLE TO VERIFY AT THIS TIME. |
| | PLEASE SEE 230.70,230.2,230.71,230.72, |
| | 240.4,310.16,240.21 ETC. |
| | 215.5 |
| | |
| | 3) NOTE: PLEASE CLARIFY THE DIFFERENCE |
| | IN E2.1 AND 2.2. |
| | |
| | |
| | ** PLEASE BE SURE TO REVMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |