| 2006-06-01 00:00:00 | ************ UNSAT 3RD REVIEW ********* |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES DUE TO PLANS |
| | SUBMITTED. |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | PER NEC 2002 220. PLEASE SEE BOTH |
| | PREVIOUS REVIEWS REQUESTED THIS. |
| | 220.3,220.10,220.11,220.13,215.3,230.42 |
| | ETC. |
| | ALL NEW LOADS SHALL BE SHOWN BEING ADDED |
| | TO EXISITNG LOADS. |
| | PLANS ONLY MENTIONS "PROJECTED" NEW |
| | LOADS?? |
| | |
| | 2) NOTE: PLEASE INDICATE AND SHOW ALL |
| | ROOM AND AREA DESIGNATIONS ON PLANS. |
| | IE: OFFICE, BATHRMS, CLOSETS, STORAGE |
| | AREAS, ETC ETC. |
| | |
| | 3) NOTE: PLEASE SHOW THE LOCATION OF THE |
| | PANELS AND SERVICE EQUIPMENT ON PLANS. |
| | PLEASE SEE RESPONSE MENTIONS THIS IS NOW |
| | SHOWN ON REVISED PLANS, ONLY PANELS "C" |
| | AND "D" WERE LOCATED AT WHAT APPEARS TO |
| | BE UNDER STAIRS? |
| | 215.5 |
| | |
| | 4) NOTE: PLEASE SEE RISER HAS NOW BEEN |
| | REVISED ONCE AGAIN NOW SHOWING A PANEL |
| | "D" WHICH WAS NOT ON EITHER OF THE FIRST |
| | TWO REVIEWS? |
| | PLEASE SEE FIRST SET OF PLANS SHOWED |
| | ONLY A PANEL "A" AND "B", THEN A PANEL |
| | "C" WAS ADDED AND NOW A 4TH PANEL WAS |
| | ADDED. |
| | PLANS ALSO INDICATE A MAIN DIST PANEL, |
| | YET NO INFORMATION WAS SUBMITTED FOR |
| | THIS. |
| | PLEASE VERIFY ALL WHICH IS EXISTING AND |
| | WHICH IS NEW. |
| | PLEASE SEE RISER CONTAINS A VERY SMALL |
| | NOTE WHICH MENTIONS ALL IS EXISTING, YET |
| | PANELS DO NOT CONTAIN ANY CHECK OR MARK |
| | LOCATED IN THE PANEL DISCRIPTION |
| | INDICATING NEW OR EXISTING? |
| | PLEASE SEE RISER STILL NOT INDICATE SIZE |
| | OF SERVICE WHICH LOADS ARE ONOR BEING |
| | ADDED TO. |
| | 215.5 |
| | |
| | 5) NOTE: PLEASE COMPLETE CIRCUITING ON |
| | PLANS. |
| | SEE WAREHOUSE AREA. LTS ARE SHOWN, |
| | HOWEVER NO CONTROLS ETC. |
| | 215.5 |
| | |
| | 6) NOTE: PLEASE SEE THE PREVIOUS REVIEWS |
| | WITH RESPECT TO THE CIRCUITING OF EM AND |
| | EXT LTS. |
| | PLEASE SEE THE RESPONSE LTR MENTIONS |
| | CIRCUITING MEETS 700.12E , HOWEVER |
| | PLEASE SEE ALL EM/EXT LTS SHALL BE |
| | CIRCUITED TO THE SAME BRANCH CIRCUIT FOR |
| | LIGHTING IN ANY ONE AREA. (IF LTS IN |
| | THAT ARE GO OUT, THE EMERGENCY LIGHTING |
| | WILL COME ON. |
| | PLEASE CORRELATE AND ADJUST ALL |
| | CIRCUITING ON PLANS AND PANEL SCHEDULES. |
| | |
| | 7) NOTE: PLEASE SEE FBC CHAPTER 13 WAS |
| | NOTED IN PREVIOUS REVIEW AND RESPONSE |
| | MENTIONS THIS WILL BE UNDER SEPARATE |
| | PERMIT/WORK? |
| | PLEASE KNOW,ALL THIS INFORMATION IS |
| | REQUIRED AT THIS TIME FOR REVIEW OF CODE |
| | COMPLIANCE. |
| | THIS SCOPE OF WORK ON PLAN AS SHOWN |
| | REQUIRES THIS INFORMATION AT THIS TIME. |
| | PLEASE PROVIDE VOLTAGE DROP WORST CASE |
| | PER 13-413.1ABC.1, |
| | PLEASE SEE 13-415.1.ABC.1.1, .2, .3. |
| | SCHEDULING, OVERIDES, ETC TO BE SHOWN. |
| | |
| | 8) NOTE: PLEASE CLARIFY THE LOW VOLTGE |
| | SHOWN ON PREVIOUS TWO SETS OF PLANS |
| | SUBMITTED WERE NOT SUBMITTED WITH NEW |
| | PLANS?? IF THE LV IS NOT GOING TO BE |
| | INCLUDED, THEN ANY LV WILL BE REQUIRED |
| | TO BE UNDER SEPARATE PERMIT, PLANS AND |
| | FEES. |
| | THIS IS ONLY NOTED. |
| | |
| | 9) NOTE: PLEASE SEE PREVIOUS NOTES GAVE |
| | A NOTICE TO FLORIDA STATUES 553.80(2)(B) |
| | WITH RESPECT TO THE DESIGN PROFESSIONALS |
| | AND REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | PLEASE KNOW, DUE TO ONE OR MORE OF THE |
| | COMMENTS BEING THE SAME FOR THE THIRD |
| | REVIEW, A 4X PLAN REVIEW FEE WAS ADDED |
| | AS REQUIRED BY THE FS. |
| | PLEASE KNOW, A FEEOF $3600.00 WAS ADDED |
| | FOR THE PLAN REVIEW PORTION. |
| | THIS FEE IS BASED ON 30% OF THE BASE |
| | PERMIT FEE TIMES FOUR. THIS FEE IS |
| | REQUIRED TO BE PAID BEFORE SUBMITTING |
| | PLANS FOR FOURTH REVIEW. |
| | ** PLEASE KNOW, ONE COPY OF ALL THREE |
| | SETS OF PLANS ARE NOW BEING RETAINED BY |
| | THIS OFFICE FOR POSSIBLE REVIEW BY THE |
| | STATE OF FLORIDA BOARD OF ARCHITECTS AND |
| | LEGAL COUNSEL TO THE BOARD. |
| | ** PLEASE KNOW, IT IS RECOMMENDED A |
| | MEETING BE SET UP TO GO OVER PLANS AND |
| | COMMENTS TO HELP ALLEAVIATE ANY SUCH |
| | ADDITIONAL FEESAND ANY FURTHER DELAYS |
| | IN THE PROJECT START DATE. |
| | PLEASE SEE COPY THE THE FS IS ATTACHED |
| | ONCE AGAIN. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW AND PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE TO GO OVER |
| | COMMENTS OR QUESTIONS. |
| | |