| 2006-04-19 00:00:00 | PAUL SCHMITZ |
| | [email protected] |
| | FBC 2004 PLUMBING CODE PLAN REVIEW |
| | FBC2004 FUEL GAS CODEPLAN REVIEW |
| | FBC 2004 CH 11, FL ACESSIBILITY CODE |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | |
| | CHAPT.1, ADMINISTRATION, 2004 EDITION |
| | |
| | UNSAT |
| | 1)SHT CS, PREVIOUS NOTES NOT ADDRESSED. |
| | URINAL,EYE WASH AND BREAK ROOM SINKS NOT |
| | SHOWN ON BUILDING DATA FIXTURE COUNT. |
| | |
| | 2)SHT A-2 SHOW LOCATION OF DRINKING |
| | FOUNTAIN. |
| | 3) SHT A-4 DETAILS CORELATE DETAILS FOR |
| | THE LUNCH ROOM SINK AND COFFEE COUNTER |
| | SINK. |
| | 4) SHT A-2 11-4.24 SINKS.NO DOORS ON |
| | CABINETS, SHOW CLEAR FLOOR SPACE. |
| | 11-4.24.1 GENERAL. |
| | SINKS REQUIRED TO BE ACCESSIBLE BY |
| | SECTION 11-4.1 SHALL COMPLY WITH SECTION |
| | 11-4.24. |
| | 11-4.24.4 DEPTH. |
| | EACH SINK SHALL BE A MAXIMUM OF 6? |
| | INCHES (165 MM) DEEP. |
| | 11-4.24.5 CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR SPACE AT LEAST 30 INCHES |
| | BY 48 INCHES (760 MM BY 1219 MM) |
| | COMPLYING WITH SECTION 11-4.2.4 SHALL BE |
| | PROVIDED IN FRONT OF A SINK TO ALLOW |
| | FORWARD APPROACH. THE CLEAR FLOOR SPACE |
| | SHALL BE ON AN ACCESSIBLE ROUTE AND |
| | SHALL EXTEND A MAXIMUM OF 19 INCHES (485 |
| | MM) UNDERNEATH THE SINK (SEE FIGURE |
| | 11-32). |
| | 11-4.24.7 FAUCETS. |
| | FAUCETS SHALL COMPLY WITH SECTION |
| | 11-4.27.4. LEVER-OPERATED, PUSH-TYPE, |
| | TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED |
| | MECHANISMS ARE ACCEPTABLE DESIGNS. |
| | 5) SHT A-2 VENDING MACHINE.PROVIDE |
| | INFORMATION ON INDIRECT WASTE FOR |
| | VENDING MACHINES. |
| | 6) SHT P-1 CORELATE PLUMBING FIXTURE |
| | SCHEDULE WITH FIXTURE LAYOUT. |
| | 7) SHT P-1,2SHOW ACCESIBLELOCATION |
| | OF WATER HEATER. |
| | 607.3 THERMAL EXPANSION CONTROL. |
| | A MEANS OF CONTROLLING INCREASED |
| | PRESSURE CAUSED BY THERMAL EXPANSION |
| | SHALL BE PROVIDED WHERE REQUIRED IN |
| | ACCORDANCE WITH SECTIONS 607.3.1 AND |
| | 607.3.2. |
| | 607.3.1 PRESSURE-REDUCING VALVE. |
| | FOR WATER SERVICE SYSTEM SIZES UP TO AND |
| | INCLUDING 2 INCHES (51 MM), A DEVICE FOR |
| | CONTROLLING PRESSURE SHALL BE INSTALLED |
| | WHERE, BECAUSE OF THERMAL EXPANSION, THE |
| | PRESSURE ON THE DOWNSTREAM SIDE OF A |
| | PRESSURE-REDUCING VALVE EXCEEDS THE |
| | PRESSURE-REDUCING VALVE SETTING. |
| | 607.3.2 BACKFLOW PREVENTION DEVICE OR |
| | CHECK VALVE. |
| | WHERE A BACKFLOW PREVENTION DEVICE, |
| | CHECK VALVE OR OTHER DEVICE IS INSTALLED |
| | ON A WATER SUPPLY SYSTEM UTILIZING |
| | STORAGE WATER HEATING EQUIPMENT SUCH |
| | THAT THERMAL EXPANSION CAUSES AN |
| | INCREASE IN PRESSURE, A DEVICE FOR |
| | CONTROLLING PRESSURE SHALL BE INSTALLED. |
| | 8)SHT P-2 WATER RISER |
| | SECTION 606 INSTALLATION OF THE BUILDING |
| | WATER DISTRIBUTION SYSTEM |
| | 606.1 LOCATION OF FULL-OPEN VALVES. |
| | FULL-OPEN VALVES SHALL BE INSTALLED IN |
| | THE FOLLOWING LOCATIONS: |
| | 1. ON THE BUILDING WATER SERVICE PIPE |
| | FROM THE PUBLIC WATER SUPPLY NEAR THE |
| | CURB. |
| | 2. ON THE WATER DISTRIBUTION SUPPLY PIPE |
| | AT THE ENTRANCE INTO THE STRUCTURE. |
| | 3. ON THE BASE OF EVERY WATER RISER PIPE |
| | IN OCCUPANCIES OTHER THAN |
| | MULTIPLE-FAMILY RESIDENTIAL OCCUPANCIES |
| | THAT ARE TWO STORIES OR LESS IN HEIGHT |
| | AND IN ONE- AND TWO-FAMILY RESIDENTIAL |
| | OCCUPANCIES. |
| | 4. ON THE TOP OF EVERY WATER DOWN-FEED |
| | PIPE IN OCCUPANCIES OTHER THAN ONE- AND |
| | TWO-FAMILY RESIDENTIAL OCCUPANCIES. |
| | 9) SHT P-2 WATER HAMMER ARRESTORS SHOWN |
| | AT TOP OF RISER IS NOT PER THE |
| | MANFACTURE INSTALLATION INSTRUCTIONS. |
| | SHOULD BE AT POINT OF SERVICE, OR |
| | BETWEEN THE LAST TWO FIXTURES. |
| | 10) SHT P-2 WATER AND SANITARY RISRER IS |
| | NOT SHOWING ALL OFF THE FIXTURES.I COUNT |
| | AT LEAST 14 FIXTURES. |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |
| | |