| Plan Review Notes For Permit 05111159 |
| Permit Number |
05111159 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-04-06 00:00:00 | ******DENIED****** | | | | | | 1) EXITS AND EMERGENCY LIGHTING ARE | | | ILLUSTRATED DIFFERENTLY ON EACH SHEET. | | | PLEASE CORRULATE, AND CLEARLY IDENTIFY | | | LOCATIONS. ARE THERE ENOUGH EXITS IN | | | WAREHOUSE AREAS? SHT A-5 WAS INDICATED | | | FOR REFERENCE, HOWEVER THAT SHEET HAS | | | BEEN VOIDED. SHT E-1.1 DOES NOT SHOW ANY | | | EMERGENCY LIGHTING IN AREA 116. | | | | | | 2) DETAILS FOR STORAGE RACKS ARE | | | REQUIRED FOR REVIEW PRIOR TO APPROVAL OF | | | DRAWINGS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLANS REVIEW (561) 805-6722 |
|