| 2006-03-23 00:00:00 | *** UNSAT 2ND REVIEW *** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND NEW NOTES FOR INFORMATION |
| | ADDED TO PLANS. |
| | FIRST SET OF NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM FIRST REVIEW. |
| | |
| | ************* UNSAT ************** |
| | |
| | 1)NOTE: OK |
| | |
| | 2)NOTE:OK/ NO, HSEE NEW NOTES FOR |
| | CIRCUIT. PLEASE ALSO SEE ROOM AND AREA |
| | DESIGNATIONS WERENOT REVISED. |
| | |
| | 3)NOTE: NO, PLEASE SHOW ALL PANEL |
| | LOCATIONS. NEED TO VERIFY 11.26,240.24, |
| | 407.7 ETC |
| | |
| | **PRE REVIEW ** |
| | PLEASE SEE LEGEND NOTES SHOWS |
| | METER AND PANELS, HOWEVER THESE COULD |
| | NOT BE LCOATE DON PLANS. PLEASE SHOW |
| | PANEL LOCATIONS. PLEASE BE SURE TO SEE |
| | 110.26, 240.24. |
| | 215.5 |
| | |
| | 4)NOTE: NO, PLEASE SEE THE LOADS WHICH |
| | WERE SUBMITTED SEEM ONLY TO BE FOR NEW |
| | LOADS ADDED AND LENDS NO INFORMATION FOR |
| | EXISTING LOADS THIS LOAD IS ADDED TO AND |
| | THE SIZE OF EXISTING SERVICE AS BEING |
| | NOTED. |
| | NEED TO VERIFY CAPACITY ETC. |
| | PLEASE ALSO VERIFY ALL CONTINOUS LOADS( |
| | LIGHTING) AT 125%. |
| | |
| | ** PRE-REVIEW** |
| | PLEASE SUBMIT LOAD CALCULATIONS |
| | FOR SAID PANELS. |
| | ARE THEY FED FROM OTHER PANELS? OR IS |
| | THE TWO PANELS SUBMITTED THE ONLY PANELS |
| | FROM SERVICE? |
| | PLEASE SEE THE ONLY ITEMS SHOWN ON PANEL |
| | SCHEDULES ARE LTS AND RECEPTS? |
| | ARE OTHER LOADS, A/C ETC ON OTHER |
| | PANELS? |
| | PLEASE BE SURE TO SEE 220.10, 220.3, |
| | 220.11, 220.13, ETC |
| | PLEASE ALSO SHOW ALL CONTINUOUS LOADS |
| | @125%. LIGHTING/LARGEST MOTOR. ETC |
| | |
| | 6)NOTE:OK. |
| | |
| | 7)NOTE:NO, COULD NOT LOCATE AS |
| | RESPONSE LTR MENTIONS THESE ARE ADDED. |
| | |
| | ** PRE REVIEW ** |
| | PLEASE SEE NO RECEPTS ARE SHOWN |
| | IN BATH RM(S) OR KITCHEN/LUNCH ROOM? |
| | PLEASE VERIFY. |
| | PLEASE SEE 2002 NEC 210.8B, 210.8B3 |
| | WHICH REQUIRES ALL 15- AND 20-AMPERE, |
| | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE |
| | KITCHENS TO BE GFCI PROTECTED. THIS |
| | REQUIREMENT APPLIES TO EACH AND EVERY |
| | 15- AND 20-AMPERE, 125-VOLT KITCHEN |
| | RECEPTACLE, WHETHER OR NOT THE |
| | RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| | |
| | 8)NOTE:NO, PLEASE SEE RESPONSE LTR |
| | MENTIONS THE TITLE BLOCKS WERE REVISED, |
| | HOWEVER THE "PRINTED NAME AND PRINTED |
| | LICENSE NUMBER " OF ARCHITECT COULD NOT |
| | BE LOCATED ON SAID TITLE BLOCKS AS |
| | REQUIRED. |
| | |
| | ** PRE- REVIEW ** |
| | PLEASE SEE FAC 61G1-16.004 WHICH |
| | ALSO REQUIRES THE PRINTED NAME AND |
| | LICENSE # OF SAID ARCHITECT. |
| | PLEASE KNOW THIS IS REQUIRED OF ALL |
| | TRADES AND FOR ALL SHEETS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 9)NOTE: OK. |
| | |
| | 10)NOTE:NO, PLEASE SEE THIS PROJECT IS |
| | ON "OKEECHOBEE RD AND PLANS NEED TO |
| | REFLECT THIS.OLD OKEECHOBEE IS NOT |
| | ACCURATE. IT IS KNOWN TO THIS OFFICE |
| | THAT PBCPA OFFICE INDICATES THIS AS "OLD |
| | " AND THE STREET SIGNS EVEN INDICATE |
| | THIS. |
| | PLEASE SEE BLDG REVIEW. |
| | |
| | ** PRE- NOTES** |
| | PLEASE SEE PERMIT APPLICATION |
| | AND PLANS BOTH MENTIONS "OLD" |
| | OKEECHOBEE. |
| | PLEASE KNOW AND PLEASE SEE PALM BEACH |
| | COUNTY PROPERY APPRAISER'S RECORDS AND |
| | CITY OF WEST PALM BEACH RECORDS FOR THIS |
| | PCN NUMBER IS FOR "OKEECHOBEE RD". |
| | PLEASE ADJUST PLANS ETC. |
| | |
| | NEW NOTES** |
| | |
| | 1) NOTE: PLEASE SEE CIRCUITING IS NOW |
| | SHOWN, HOWEVER PLEASE SEE 700.12E WHICH |
| | REQUIRES ALL EM/EXT LTS TO BE CIRCUITED |
| | TO THE LOCAL BRANCH CIRCUIT IN THE AREA |
| | IN WHICH THESE ARE LOCATED. |
| | |
| | 2)NOTE: PLEASE SEE FBC 2004, CHAPTER 13, |
| | |
| | PLEASE PROVIDE WORST CASE VDPER |
| | 13-413.1ABC.1 |
| | PLEASE PROVIDE ALL AUTOMATED SYSTEM(S) |
| | INFORMATION AS REQUIRED PER |
| | 13-415.1.ABC.1 AND .2 |
| | PLEASE SUBMIT SCHEDULING, OVERRIDES, |
| | OCCUPANCY SENSOR INFORMATION AND TYOE OF |
| | SYSTEM TO BE INSTALLED. |
| | CIRCUITING WAS NOT SHOWN ON PREVIOUS |
| | PLANS. |
| | |
| | 3) NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| | RESPECT TO DESIGN PROFESSIONAL AND |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | THIS IS ONLY A NOTICE. |
| | |
| | |
| | ** PLEASE SEE ANY OTHER POSSIBLE |
| | COMMENTS FROM OTHER REVIEWER(S) WHICH |
| | MAY AFFECT ELECTRICAL PLANS. |
| | |
| | |
| | *************************************** |
| | ** PLEASE DO NOT ATTACHED THE OLD SETS |
| | TO THE NEW SETS. ONLY ONE OLD SET SHOULD |
| | BE SUBMITTED AND THIS SET SHOULD BE |
| | SEPARATE. |
| | ************************************* |
| | |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE SET OF ANY OLD/VOIDED |
| | REMOVED SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2006-03-22 00:00:00 | IN ELEC FOR REVIEW. |