2006-04-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05111159
 ADD: 1600 OKEECHOBEE RD
 CONT: THORTON & THORTON INC
 TEL: (321)229-3406
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2A) COMPLIED
 2B) COMPLIED
 2C) COMPLIED
 2D) COMPLIED
 2E)FROM PREVIOUS REVIEW, IF AN AUTOMATIC
 SPRINKLER SYSTEM ISPROVIDED, WHETHER
 THE SPRINKLER SYSTEM IS REQUIRED. IF THE
 FIRE SPRINKLER IS PROVIDED OR REQUIRED
 BY CODE THEN THE FIRE SPRINKLER PLANS
 SHALL BE INCLUDED IN THE BUILDING PERMIT
 PACKAGE BEFORE ISSUANCE OF THIS PERMIT.
 NOTE FIRE SPRINKLER PERMIT AND FIRE
 SPRINKLER PLANS ARE REQUIRED SEPERATELY.
 2F) COMPLIED AT THIS TIME.
  
 3)FROM THE PREVIOUS REVIEW, 3) PROVIDE A
 CURRENT SURVEY OF THE BUILDING,(2004
 FBC) 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE & EXTENT OF THE WORK
 PROPOSED & SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND REVELENT LAWS, ORDINANCES, AND RULES
 AND REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 4)FROM THE PREVIOUS REVIEW, NOT
 ADDRESSED IN RESPONCE SHEET.
 IT APPEARS THAT THE SO CALLED MEZANINE
 NO LONGER MEETS THE DEFINITION SINCE THE
 AREA BELOW THE MEZANINE CAN'T BE FIGURED
 INTO THE CLEAR FLOOR AREA.
  
 505.2 AREA LIMITATION.
 THE AGGREGATE AREA OF A MEZZANINE OR
 MEZZANINES WITHIN A ROOM SHALL NOT
 EXCEED ONE-THIRD OF THE AREA OF THAT
 ROOM OR SPACE IN WHICH THEY ARE LOCATED.
 THE ENCLOSED PORTIONS OF ROOMS SHALL NOT
 BE INCLUDED IN A DETERMINATION OF THE
 SIZE OF THE ROOM IN WHICH THE MEZZANINE
 IS LOCATED. IN DETERMINING THE ALLOWABLE
 MEZZANINE AREA, THE AREA OF THE
 MEZZANINE SHALL NOT BE INCLUDED IN THE
 AREA OF THE ROOM.
  
 5) COMPLIED
  
 6) COMPLIED
  
 7A) FROM THE PREVIOUS REVIEW,
 7) PROVIDE EGRESS PATHWAYS FOR THE
 WAREHOUSE AREAS,116 & 117. THE PLAN
 SHOWS A EGRESS AISLE IN 116 TO A EXIT
 AND BACK INTO THE OFFICE OCCUPANCY. NOTE
 THE OCCUPANTS OF THE OFFICE SHOULD NOT
 BE TAKEN INTO THE WAREHOUSE STORAGE
 OCCUPANCY AS PART OF AN EGRESS UNLESS IT
 IS IN A RATED CORRIDOR! THE EXIT
 LIGHTINTHE OFFICE AREA THATLEADS INTO
 THE STORAGE AREA SHOULD BE REMOVED
 UNLESS A RATED CORRIDOR.
 1032.4.1
 IN GROUP S1 STORAGE, OCCUPANCIES COMMON
 PATH OF TRAVEL SHALL NOT EXCEED 50 FEET
 (15 M).
 EXCEPTION: COMMON PATHS OF TRAVEL SHALL
 NOT EXCEED 100 FEET (30 M) IN BUILDINGS
 PROTECTED BY AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026