| 2006-02-18 00:00:00 | PLUMBING PLAN REVIEW EXAMINER |
| | PAUL SCHMITZ 561-805-6692 |
| | [email protected] |
| | FBC PLUMBING 2004 |
| | FBC FUEL GAS 2004 |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE |
| | CH 1, ADMINISTRATION, 2004 EDITION |
| | ( ATFBC) |
| | FBC BUILDING 2004, CH 11 |
| | DENIED |
| | |
| | 1)SHT CS BUILDING DATA |
| | MINIMUM FACILITIES TABLE 403.1 |
| | MIXED USE, NUMBER OF W/C ON PLANS, FOUR. |
| | FOURREQUIRED. |
| | REST RM 113, URNIAL IS NOT SHOWN IN |
| | FIXTURE COUNT. |
| | LAVATORIES: THREE SHOWN, THREE REQUIRED. |
| | DRINKING FOUNTAIN: ONE REQUIRED. |
| | EYE WASH SHOWER: ONE REQUIRED SEC 411. |
| | SERVICE SINK: NOT SHOWN ON FIXTURE COUNT |
| | ONE SHOWN IN ROOM 109. |
| | MERCHANTILE: MEN, WOMEN.1-W/C, 1-LAV. |
| | 1-D/F, 1-S/S. |
| | STORAGE: MEN, WOMEN, 1-W/C, 1-LAV, |
| | 1- EYE WASH SHOWER, SEC 411 |
| | BUSINESS: MEN,WOMEN 1-W/C,1-LAV.1-D/F. |
| | |
| | 2) SHT CS SHEET INDEX SHOWS P-1,P-2 NOT |
| | INCLUDED IN SUBMITTED SET OF PLANS. |
| | |
| | 3) (ATFBC) SEC 106.3.5.1.3 (3)(4) |
| | COMMERICAL BUILDINGS, PLUMBING SANITARY |
| | DRAINAGE, WATER PIPING ISOMETRIC REQ. |
| | 3) SHT A-4 DETAIL B-A-4 DINENSION ON W/C |
| | OFF WALL IS 18 INCHES. |
| | |
| | 4) SECTION 11-4 |
| | ACCESSIBLE ELEMENTS AND SPACES: |
| | SCOPE AND TECHNICAL REQUIREMENTS |
| | 11-4.1 MINIMUM REQUIREMENTS. |
| | 11-4.1.1 APPLICATION. |
| | (1) GENERAL. THIS CODE ESTABLISHES THE |
| | MINIMUM STANDARDS FOR THE ACCESSIBILITY |
| | OF BUILDINGS AND FACILITIES BUILT OR |
| | ALTERED WITHIN THE STATE. |
| | (A) ALL AREAS OF NEWLY DESIGNED OR NEWLY |
| | CONSTRUCTED BUILDINGS AND FACILITIES |
| | REQUIRED TO BE ACCESSIBLE BY SECTION |
| | 11-4.1.2 AND SECTION 11-4.1.3 AND |
| | ALTERED PORTIONS OF EXISTING BUILDINGS |
| | AND FACILITIES REQUIRED TO BE ACCESSIBLE |
| | BY SECTION 11-4.1.6 SHALL COMPLY WITH |
| | THIS CODE, SECTION 11-4.1 THROUGH |
| | SECTION 11-4.35, UNLESS OTHERWISE |
| | PROVIDED IN THIS SECTION OR AS MODIFIED |
| | IN A SPECIAL APPLICATION SECTION. |
| | SHOW ELEVATIONS, DIMIENSIONS, TURNING |
| | SPACE FOR REQUIRED PLUMBING FIXTURES. |
| | |
| | |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |
| | |
| | |