2005-12-21 00:00:001. WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ 2003 EDITION NOT 2001
 EDITION.
  
 2. ALL DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 3. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 4. ALL EXITS ARE TO REMIAN CLEAR AND
 UNOBSTRUCTED.
  
 5. GASOLINE POWERED EQUIPMENT SHOULD NOT
 BE USED INDOORS DUE TO THE RISK OF
 CARBON MONIXIDE BUILD-UP.
  
 6. SEPERATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE SPRINKLER SYSTEM
 MODIFICATION.
  
 7. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 8. SECURITY PLAN APPEARS TO BE ABSENT OF
 DEVICES THAT ARE REFLECTED IN THE KEY ON
 PAGE E3.1.
  
 9. PLEASE ILLUSTRATE EXIT SIGNS AND
 EMERGENCY LIGHTING IN WAREHOUSE AREA
 116, AND 117.
  
 10. SEPERATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE ALARM SYSTEM REMODELING.
  
 11. PLEASE PROVIDE MORE DETAILS ON
 BATTERY CHARGER EQUIPMENT CONTAINED IN
 WAREHOUSE 116.
  
 12. PLEASE PROVIDE DETAILS ON STORAGE
 RACKS ILLUSTRATED WITHIN THE PLANS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION