Plan Review Notes
Plan Review Notes For Permit 05111159
Permit Number 05111159
Review Stop E
Sequence Number 1
Notes
Date Text
2005-12-24 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE FIRE REVIEW NOTES,
 PLEASE SEE AS OF JAN 1ST, 2005 WE ARE
 CURRENTLY UNDER THE 2003 LS-101
  
 2)NOTE: PLEASE SHOW ALL CIRCUTING ON
 PLANS AND CORRELATE WITH THE PANEL
 SCHEDULES SUBMITTED.
 PLEASE KNOW, EACH CIRCUIT SHALL BE
 IDENTIFIED FOR EACH PANEL. A,B ETC.
 ROOM AND AREA DESIGANTIONS SHALL ALSO BE
 PLACED ON PLANS, WHICH WILL CORRELATE
 WITH THE CIRCUITING ON PANEL SCHEDULE.
 PANEL SCHEDULE SHOULD NOTE BATHRM
 CIRCUIT# X. ETC.
 215.5
  
 3)NOTE: PLEASE SEE LEGEND NOTES SHOWS
 METER AND PANELS, HOWEVER THESE COULD
 NOT BE LCOATE DON PLANS. PLEASE SHOW
 PANEL LOCATIONS. PLEASE BE SURE TO SEE
 110.26, 240.24.
 215.5
  
 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR SAID PANELS.
 ARE THEY FED FROM OTHER PANELS? OR IS
 THE TWO PANELS SUBMITTED THE ONLY PANELS
 FROM SERVICE?
 PLEASE SEE THE ONLY ITEMS SHOWN ON PANEL
 SCHEDULES ARE LTS AND RECEPTS?
 ARE OTHER LOADS, A/C ETC ON OTHER
 PANELS?
 PLEASE BE SURE TO SEE 220.10, 220.3,
 220.11, 220.13, ETC
 PLEASE ALSO SHOW ALL CONTINUOUS LOADS
 @125%. LIGHTING/LARGEST MOTOR. ETC
  
 6)NOTE: PLEASE INDICATE NEW OR EXSITING
 SIGN CIRCUIT REQUIRED PER 600.5 AT FRONT
 DOOR LOCATION.
  
 7)NOTE: PLEASE SEE NO RECEPTS ARE SHOWN
 IN BATH RM(S) OR KITCHEN/LUNCH ROOM?
 PLEASE VERIFY.
 PLEASE SEE 2002 NEC 210.8B, 210.8B3
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
 8)NOTE: PLEASE SEE FAC 61G1-16.004 WHICH
 ALSO REQUIRES THE PRINTED NAME AND
 LICENSE # OF SAID ARCHITECT.
 PLEASE KNOW THIS IS REQUIRED OF ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 9)NOTE: PLEASE SEE SHEET 4 OF 5 IN ONE
 SETIS NOT SEALED BY SAID ARCHITECT.
 FS 481.221
  
 10)NOTE: PLEASE SEE PERMIT APPLICATION
 AND PLANS BOTH MENTIONS "OLD"
 OKEECHOBEE.
 PLEASE KNOW AND PLEASE SEE PALM BEACH
 COUNTY PROPERY APPRAISER'S RECORDS AND
 CITY OF WEST PALM BEACH RECORDS FOR THIS
 PCN NUMBER IS FOR "OKEECHOBEE RD".
 PLEASE ADJUST PLANS ETC.
  
  
 ** PLEASE SEE ANY OTHER POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE SET OF ANY OLD/VOIDED
 REMOVED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]