Plan Review Notes
Plan Review Notes For Permit 05111159
Permit Number 05111159
Review Stop B
Sequence Number 1
Notes
Date Text
2006-02-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05111159
 ADD: 1600 OKEECHOBEE RD
 CONT: THORTON & THORTON INC
 TEL: (321)229-3406
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 3) PROVIDE ACURRENT SURVEY OF THE
 BUILDING,(2004 FBC) 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE & EXTENT OF THE WORK
 PROPOSED & SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND REVELENT LAWS, ORDINANCES, AND RULES
 AND REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 4) IT APPEARS THAT THE SO CALLED
 MEZANINE NO LONGER MEETS THE DEFINITION
 SINCE THE AREA BELOW THE MEZANINE CAN'T
 BE FIGURED INTO THE CLEAR FLOOR AREA.
  
 505.2 AREA LIMITATION.
 THE AGGREGATE AREA OF A MEZZANINE OR
 MEZZANINES WITHIN A ROOM SHALL NOT
 EXCEED ONE-THIRD OF THE AREA OF THAT
 ROOM OR SPACE IN WHICH THEY ARE LOCATED.
 THE ENCLOSED PORTIONS OF ROOMS SHALL NOT
 BE INCLUDED IN A DETERMINATION OF THE
 SIZE OF THE ROOM IN WHICH THE MEZZANINE
 IS LOCATED. IN DETERMINING THE ALLOWABLE
 MEZZANINE AREA, THE AREA OF THE
 MEZZANINE SHALL NOT BE INCLUDED IN THE
 AREA OF THE ROOM.
 THE PLANS DO NOT INDICATE WHAT TYPE
 OF OCCUPANCY THE ROOM WILL BE AT THE
 HEAD OF THE STAIRS, MAY REQUIRE A SECOND
 MEANS OF EGRESS, ( ENCLOSED STAIR)?
  
 5) PLANS DO NOT PROVIDE WHAT TYPE OF
 MATERIAL WILL BE STORED IN WAREHOUSE
 116 OR 117? THIS MAY REQUIRE EITHER A 1
 HR RATED WALL BETWEEN OFFICE AND
 WAREHOUSE ONCE DECLARE WHAT TYPE OF
 MATERIALS ARE TO BE STORED?S1 VS S2?
  
 6) PLANS ALSO INDICATE BATTERY CHARGER
 AND GUARDRAIL? EXPLAIN THE USAGE, AND
 AMOUNT OF BATTERIES?
  
 7) PROVIDE EGRESS PATHWAYS FOR THE
 WAREHOUSE AREAS, E1.1 DOES NOT INDICATE
 EXIT LIGHTS IN WAREHOUSE AREA.1016.1.1
 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH THIS SECTION
 FOR EVERY BUILDING AND STRUCTURE.FOR
 THE PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS AND PASSAGEWAYS LEADING TO AN
 EXIT.FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS,WALKWAYS
 AND EXIT PASSAGEWAYS LEADING TO A PUBLIC
 WAY.
  
 8) SHEET E4.1 MISSING SEAL ON ONE SET OF
 PLANS.PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026